The PowerFlex 4 is designed so that start up is simple and efficient. The Program Group 
contains the most commonly used parameters.

Smart Start-Up with Basic Program Group Parameters

= Stop drive before changing this parameter.

No.

Parameter

Min/Max

Display/Options

Default

P031 [Motor NP Volts]

20/Drive Rated Volts

1 VAC

Based on Drive Rating

Set to the motor nameplate rated volts.

P032 [Motor NP Hertz]

10/240 Hz

1 Hz

60 Hz

Set to the motor nameplate rated frequency.

P033 [Motor OL Current]

0.0/(Drive Rated Amps

×

2) 0.1 Amps

Based on Drive Rating

Set to the maximum allowable motor current.

P034 [Minimum Freq]

0.0/240.0 Hz

0.1 Hz

0.0 Hz

Sets the lowest frequency the drive will output 
continuously.

P035 [Maximum Freq]

0/240 Hz

1 Hz

60 Hz

Sets the highest frequency the drive will output.

P036  [Start Source]

0/5

0 = “Keypad”

(1)

 

1 = “3-Wire”
2 = “2-Wire”
3 = “2-Wire Level Sensitive”
4 = “2-Wire High Speed”
5 = “RS485 (DSI) Port”

0

Sets the control scheme used to start the drive.

(1) 

When active, the Reverse key is also active 

unless disabled by A095 [Reverse Disable].

P037 [Stop Mode]

0/7

0 = “Ramp, Clear Fault”

(1) 

1 = “Coast, Clear Fault”

(1)

 

2 = “DC Brake, Clear Fault”

(1)

 

3 = “DC Brake w/Shutoff, Clear Fault”

(1)

 

4 = “Ramp”
5 = “Coast”
6 = “DC Brake”
7 = “DC Brake w/Shutoff”

0

Active stop mode for all stop sources [e.g. keypad, 
run forward (I/O Terminal 02), run reverse (I/O 
Terminal 03), RS485 port] except as noted below.

Important:

 I/O Terminal 01 is always a coast to 

stop input except when P036 [Start Source] is set 
for “3-Wire” control. When in three wire control, I/O 
Terminal 01 is controlled by P037 [Stop Mode].

(1) 

Stop input also clears active fault.

P038 [Speed Reference]

0/5

0 = “Drive Potentiometer”
1 = “Internal Freq”
2 = “0-10V Input/Remote Potentiometer”
3 = “4-20mA Input”
4 = “Preset Freq 0-3”
5 = “RS485 (DSI) Port”

0

Sets the source of the speed reference to the 
drive.

Important:

 When A051 or A052 [Digital Inx Sel] is 

set to option 2, 4, 5 or 6, and the digital input is 
active, A051 or A052 will override the speed 
reference commanded by this parameter. Refer to 
Chapter 1 of the PowerFlex 4 

User Manual 

on CD 

for details.

P039 [Accel Time 1]

0.0/600.0 Secs

0.1 Secs

10.0 Secs

Sets the rate of accel for all speed increases.

P040 [Decel Time 1]

0.1/600.0 Secs

0.1 Secs

10.0 Secs

Sets the rate of decel for all speed decreases.

P041 [Reset To Defaults]

0/1

0 = “Idle State”
1 = “Reset Defaults”

0

Resets all parameter values to factory defaults.

Advanced Group Parameters

No.

Parameter

Min/Max

Display/Options

Default

A051

A052

[Digital In1 Sel]

I/O Terminal 05

[Digital In2 Sel]

I/O Terminal 06

0/7

0 = “Not Used”
1 = “Accel 2 & Decel 2”
2 = “Jog”
3 = “Auxiliary Fault”

4 = “Preset Frequencies”
5 = “Local”
6 = “RS485 (DSI) Port”
7 = “Clear Fault”

4

A055 [Relay Out Sel]

0/9

0 = “Ready” (Not Faulted)
1 = “At Frequency”
2 = “Motor Running”
3 = “Reverse”
4 = “Motor Overload”

5 = “Ramp Regulated”
6 = “Above Frequency”
7 = “Above Current”
8 = “Above DC Bus Volts”
9 = “Retries Exhausted”

0

A056 [Relay Out Level]

0.0/9999

0.1 – 1

0.0

A067 [Accel Time 2]

0.0/600.0 Secs

0.1 Secs

20.0 Secs

A068 [Decel Time 2]

0.1/600.0 Secs

0.1 Secs

20.0 Secs

A069 [Internal Freq]

0.0/240.0 Hz

0.1 Hz

60.0 Hz

See the PowerFlex 4 User Manual on CD for more information on parameters.

Allen-Bradley Drives

All manuals and user guides at all-guides.com

Содержание PowerFlex 4

Страница 1: ...2 Auto Rstrt Tries A094 Start At PowerUp is used in an inappropriate application Do not use this function without considering applicable local national and international codes standards regulations or...

Страница 2: ...56 1 96 Nm 14 17 lb in AmbientTemperature Enclosure Rating Minimum Mounting Clearances Minimum Maximum 10 C 14 F 40 C 104 F IP 20 Open Type Use Mounting Option A IP 30 NEMA 1 UL Type 1 1 1 Rating requ...

Страница 3: ...Efficiency 97 5 Typical Digital Control Inputs Input Current 6mA Analog Control Inputs SRC Source Mode 18 24V ON 0 6V OFF SNK Sink Mode 0 6V ON 18 24V OFF 4 20mA Analog 250 ohm input impedance 0 10V D...

Страница 4: ...endations Input Power Condition Corrective Action Low Line Impedance less than 1 line reactance Install Line Reactor 2 or Isolation Transformer Greater than 120 kVA supply transformer Line has power f...

Страница 5: ...0 ohm P038 16 RS485 DSI Shield Terminal should be connected to safety ground PE when using the RS485 DSI communications port 3 Only one analog frequency source may be connected at a time If more than...

Страница 6: ...ny Program Group parameters Start Stop Direction and Speed Control Factory default parameter values allow the drive to be controlled from the integral keypad No programming is required to start stop c...

Страница 7: ...gramming menu Cancel a change to a parameter value and exit Program Mode Select Advance one step in programming menu Select a digit when viewing parameter value Up Arrow Down Arrow Scroll through grou...

Страница 8: ...parameters that are in the group 7 Press Enter or Sel to view the value of a parameter If you do not want to edit the value press Esc to return to the parameter number 8 Press Enter or Sel to enter p...

Страница 9: ...control When in three wire control I O Terminal 01 is controlled by P037 Stop Mode 1 Stop input also clears active fault P038 Speed Reference 0 5 0 Drive Potentiometer 1 Internal Freq 2 0 10V Input R...

Страница 10: ...Mechanical 3 Both 1 A098 SW Current Trip 0 0 Drive Amps 2 0 1 Amps 0 0 Disabled A099 Process Factor 0 1 999 9 0 1 30 0 A100 Fault Clear 0 2 0 Ready 1 Reset Active Fault 2 Clear Fault Queue 0 A101 Pro...

Страница 11: ...urrent Limit F7 Motor Overload 1 An excessive motor load exists Reduce load so drive output current does not exceed the current set by parameter P033 Motor OL Current F8 Heatsink OvrTmp 1 Check for bl...

Страница 12: ...9 87 4 3 44 168 6 61 2 2 4 9 1 Overall height of drive with IP 30 NEMA 1 UL Type 1 option kit installed 2 Overall height of standard IP 20 Open Type drive Frame 120V AC 1 Phase 240V AC 1 Phase 240V AC...

Отзывы: