background image

 

English-3

 

Specifications, Fuses and Circuit Breakers

 

Drive Ratings

Catalog 
Number

Output Ratings

Input Ratings

Branch Circuit Protection

Power 
Dissipation

 

kW (HP)

Amps

Voltage 
Range

kVA

Amps

Fuses

140M Motor 
Protectors

Contactors

IP20 Open 
Watts

 

100 - 115V AC 1-Phase Input, 0 - 230V 3-Phase Output 

 

22A-V1P5N104

0.2 (0.25)

1.5

90-126

0.75

6.0

10

140M-C2E-C10 100-C09

25

22A-V2P3N104

0.37 (0.5)

2.3

90-126

1.15

9.0

15

140M-C2E-C16 100-C12

30

22A-V4P5N104

0.75 (1.0)

4.5

90-126

2.25

18.0

30

140M-D8E-C20 100-C23

50

 

200 - 240V AC – 1-Phase

 

(1)

 

 

 

Input, 0 - 230V 3-Phase Output

 

22A-A1P5N104

0.2 (0.25)

1.5

180-265

0.75

5.0

10

140M-C2E-B63 100-C09

25

22A-A2P3N104

0.37 (0.5)

2.3

180-265

1.15

6.0

10

140M-C2E-B63 100-C09

30

22A-A4P5N104

0.75 (1.0)

4.5

180-265

2.25

10.0

15

140M-C2E-C16 100-C12

50

22A-A8P0N104

1.5 (2.0)

8.0

180-265

4.0

18.0

30

140M-D8E-C20 100-C23

80

 

200 - 240V AC – 3-Phase Input, 0 - 230V 3-Phase Output

 

22A-B1P5N104

0.2 (0.25)

1.5

180-265

0.75

1.8

3

140M-C2E-B25 100-C09

25

22A-B2P3N104

0.37 (0.5)

2.3

180-265

1.15

2.5

6

140M-C2E-B40 100-C09

30

22A-B4P5N104

0.75 (1.0)

4.5

180-265

2.25

5.2

10

140M-C2E-C10 100-C09

50

22A-B8P0N104

1.5 (2.0)

8.0

180-265

4.0

9.5

15

140M-C2E-C16 100-C12

80

22A-B012N104

2.2 (3.0)

12.0

180-265

5.5

15.5

25

140M-C2E-C16 100-C16

115

22A-B017N104

3.7 (5.0)

17.5

180-265

8.6

21.0

35

140M-F8E-C25 100-C23

165

 

380 - 480V AC – 3-Phase

 

 

 

Input, 0 - 460V 3-Phase Output

 

22A-D1P4N104 0.37 (0.5)

1.4

340-528

1.4

1.8

3

140M-C2E-B25 100-C09

30

22A-D2P3N104 0.75 (1.0)

2.3

340-528

2.3

3.2

6

140M-C2E-B40 100-C09

40

22A-D4P0N104 1.5 (2.0)

4.0

340-528

4.0

5.7

10

140M-C2E-B63 100-C09

60

22A-D6P0N104 2.2 (3.0)

6.0

340-528

5.9

7.5

15

140M-C2E-C10 100-C09

90

22A-D8P7N104 3.7 (5.0)

8.7

340-528

8.6

9.0

15

140M-C2E-C16 100-C16

145

 

Input/Output Ratings

Approvals

 

Output Frequency:

 

 0-240 Hz (Programmable)

 

Efficiency:

 

 97.5% (Typical)

 

Digital Control Inputs (Input Current = 6mA)

Analog Control Inputs

 

SRC (Source) Mode:

18-24V = ON
0-6V = OFF

SNK (Sink) Mode:

0-6V = ON
18-24V = OFF

 

4-20mA Analog:

 

 250 ohm input impedance

 

0-10V DC Analog:

 

 100k ohm input impedance

 

External Pot:

 

 1-10k ohms, 2 Watt minimum

 

Control Output

 

Programmable Output (form C relay)

 

Resistive Rating: 3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC
Inductive Rating: 0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC

 

Fuses and Circuit Breakers

 

Recommended Fuse Type:

 

 UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.

 

Recommended Circuit Breakers:

 

 HMCP circuit breakers or equivalent.

 

Protective Features

 

Motor Protection:

 

 I

 

2

 

t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)

 

Overcurrent:

 

 200% hardware limit, 300% instantaneous fault

 

Over Voltage:

 

100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)
200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)
380-460V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)

 

Under Voltage:

 

100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)
200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)
380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)

 

Control Ride Through:

 

 Minimum ride through is 0.5 Secs - typical value 2 Secs

 

Faultless Power Ride Through:

 

 100 milliseconds

 

Dynamic Braking

 

Internal brake IGBT included with all ratings 0.75 kW (1 HP) and larger. Refer to Appendix B of the PowerFlex 4 

 

User Manual

 

 

on CD for ordering information.

 

(1)

 

200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N104 to N114.

UL

®

LIST

ED 966X

IND

CO N T E Q

UL508C

UL

®

LIST

ED 966X

IND

CO N T E Q

C

CSA 22.2

EMC Directive 89/336
 

LV: 

EN 50178, EN 60204

 

EMC:  EN 61800-3, EN 50081-1, EN 50082-2

Allen-Bradley Drives

All manuals and user guides at all-guides.com

Содержание PowerFlex 4

Страница 1: ...2 Auto Rstrt Tries A094 Start At PowerUp is used in an inappropriate application Do not use this function without considering applicable local national and international codes standards regulations or...

Страница 2: ...56 1 96 Nm 14 17 lb in AmbientTemperature Enclosure Rating Minimum Mounting Clearances Minimum Maximum 10 C 14 F 40 C 104 F IP 20 Open Type Use Mounting Option A IP 30 NEMA 1 UL Type 1 1 1 Rating requ...

Страница 3: ...Efficiency 97 5 Typical Digital Control Inputs Input Current 6mA Analog Control Inputs SRC Source Mode 18 24V ON 0 6V OFF SNK Sink Mode 0 6V ON 18 24V OFF 4 20mA Analog 250 ohm input impedance 0 10V D...

Страница 4: ...endations Input Power Condition Corrective Action Low Line Impedance less than 1 line reactance Install Line Reactor 2 or Isolation Transformer Greater than 120 kVA supply transformer Line has power f...

Страница 5: ...0 ohm P038 16 RS485 DSI Shield Terminal should be connected to safety ground PE when using the RS485 DSI communications port 3 Only one analog frequency source may be connected at a time If more than...

Страница 6: ...ny Program Group parameters Start Stop Direction and Speed Control Factory default parameter values allow the drive to be controlled from the integral keypad No programming is required to start stop c...

Страница 7: ...gramming menu Cancel a change to a parameter value and exit Program Mode Select Advance one step in programming menu Select a digit when viewing parameter value Up Arrow Down Arrow Scroll through grou...

Страница 8: ...parameters that are in the group 7 Press Enter or Sel to view the value of a parameter If you do not want to edit the value press Esc to return to the parameter number 8 Press Enter or Sel to enter p...

Страница 9: ...control When in three wire control I O Terminal 01 is controlled by P037 Stop Mode 1 Stop input also clears active fault P038 Speed Reference 0 5 0 Drive Potentiometer 1 Internal Freq 2 0 10V Input R...

Страница 10: ...Mechanical 3 Both 1 A098 SW Current Trip 0 0 Drive Amps 2 0 1 Amps 0 0 Disabled A099 Process Factor 0 1 999 9 0 1 30 0 A100 Fault Clear 0 2 0 Ready 1 Reset Active Fault 2 Clear Fault Queue 0 A101 Pro...

Страница 11: ...urrent Limit F7 Motor Overload 1 An excessive motor load exists Reduce load so drive output current does not exceed the current set by parameter P033 Motor OL Current F8 Heatsink OvrTmp 1 Check for bl...

Страница 12: ...9 87 4 3 44 168 6 61 2 2 4 9 1 Overall height of drive with IP 30 NEMA 1 UL Type 1 option kit installed 2 Overall height of standard IP 20 Open Type drive Frame 120V AC 1 Phase 240V AC 1 Phase 240V AC...

Отзывы: