English-5

 

Control Terminal Block

 

No.

Signal

Default

Description

Param.

 

R1

Relay N.O.

Fault

Normally open contact for output relay.

A055

R2

Relay Common

Common for output relay.

R3

Relay N.C.

Fault

Normally closed contact for output relay.

A055

Sink/Source DIP Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch 
setting.

01

Stop

 

(1)

 

Coast

The factory installed jumper or a normally closed input 
must be present for the drive to start.

P036

 

(1)

 

02

Start/Run FWD

Not Active

Command comes from the integral keypad by default. To 
disable reverse operation, see A095 [Reverse Disable].

P036, P037

03

Direction/Run REV

Not Active

P036, P037, 
A095

04

Digital Common

For digital inputs. Electronically isolated with digital inputs 
from analog I/O.

05

Digital Input 1

Preset Frequencies Program with A051 [Digital In1 Sel].

A051

06

Digital Input 2

Preset Frequencies Program with A052 [Digital In2 Sel].

A052

11

+24V DC

Drive supplied power for digital inputs.
Maximum output current is 100mA.

12

+10V DC

Drive supplied power for 0-10V external potentiometer.
Maximum output current is 15mA.

P038

13

0-10V In

 

(3)

 

Not Active

For external 0-10V input supply
(input impedance = 100k ohm) or potentiometer wiper.

P038

14

Analog Common

For 0-10V In or 4-20mA In. Electronically isolated with 
analog inputs from digital I/O.

15

4-20mA In

 

(3)

 

Not Active

For external 4-20mA input supply
(input impedance = 250 ohm).

P038

16

RS485 (DSI) Shield

Terminal should be connected to safety ground - PE when 
using the RS485 (DSI) communications port.

 

(3)

 

Only one analog frequency source may be connected at a time. If more than one reference is connected at the same 
time, an undetermined frequency reference will result.

01

02

03

04

05

06

11

12

13

14

15

16

Stop 

(1)

Start/Run FWD 

(2)

Direction/Run REV

Digital Common

Digital Input 1

Digital Input 2

R1

R2

R3

Relay N.O.

Relay Common

Relay N.C.

+24V DC

+10V DC

0-10V In

Analog Common

4-20mA In

RS485 Shield

+24V

+10V

Typical

SNK Wiring

Typical

SRC Wiring

8 1

RS485

(DSI)

R1 R2 R3

01

02

03

04

05

06

11

12

13

14

15

16

SNK

SRC

(1)

Potentiometer 
must be
1-10k ohm
2 Watt Min.

30V DC 125V AC 240V AC

Resistive

3.0A

3.0A

3.0A

Inductive

0.5A

0.5A

0.5A

(1)

 Important:

 I/O Terminal 01 is 

always a coast to stop input except 
when P036 [Start Source] is set to 
“3-Wire” control. In three wire 
control, I/O Terminal 01 is controlled 
by P037 [Stop Mode]. All other stop 
sources are controlled by P037 
[Stop Mode].

Important:

 The drive is shipped with 

a jumper installed between I/O 
Terminals 01 and 11. Remove this 
jumper when using I/O Terminal 01 
as a stop input.

(2)

 

Two wire control shown. For three 

wire control use a momentary input 

 on I/O Terminal 02 to 

command a start. Use a maintained 
input 

 for I/O Terminal 03 to 

change direction.

Refer to the PowerFlex 4 

User Manual

 on CD for 

detailed I/O wiring examples.

P036

[Start Source]

Stop

I/O Terminal 01

Stop

Keypad

Per P037

Coast

3-Wire

Per P037

Per P037

2-Wire

Per P037

Coast

RS485 Port

Per P037

Coast

Allen-Bradley Drives

All manuals and user guides at all-guides.com

Содержание PowerFlex 4

Страница 1: ...2 Auto Rstrt Tries A094 Start At PowerUp is used in an inappropriate application Do not use this function without considering applicable local national and international codes standards regulations or...

Страница 2: ...56 1 96 Nm 14 17 lb in AmbientTemperature Enclosure Rating Minimum Mounting Clearances Minimum Maximum 10 C 14 F 40 C 104 F IP 20 Open Type Use Mounting Option A IP 30 NEMA 1 UL Type 1 1 1 Rating requ...

Страница 3: ...Efficiency 97 5 Typical Digital Control Inputs Input Current 6mA Analog Control Inputs SRC Source Mode 18 24V ON 0 6V OFF SNK Sink Mode 0 6V ON 18 24V OFF 4 20mA Analog 250 ohm input impedance 0 10V D...

Страница 4: ...endations Input Power Condition Corrective Action Low Line Impedance less than 1 line reactance Install Line Reactor 2 or Isolation Transformer Greater than 120 kVA supply transformer Line has power f...

Страница 5: ...0 ohm P038 16 RS485 DSI Shield Terminal should be connected to safety ground PE when using the RS485 DSI communications port 3 Only one analog frequency source may be connected at a time If more than...

Страница 6: ...ny Program Group parameters Start Stop Direction and Speed Control Factory default parameter values allow the drive to be controlled from the integral keypad No programming is required to start stop c...

Страница 7: ...gramming menu Cancel a change to a parameter value and exit Program Mode Select Advance one step in programming menu Select a digit when viewing parameter value Up Arrow Down Arrow Scroll through grou...

Страница 8: ...parameters that are in the group 7 Press Enter or Sel to view the value of a parameter If you do not want to edit the value press Esc to return to the parameter number 8 Press Enter or Sel to enter p...

Страница 9: ...control When in three wire control I O Terminal 01 is controlled by P037 Stop Mode 1 Stop input also clears active fault P038 Speed Reference 0 5 0 Drive Potentiometer 1 Internal Freq 2 0 10V Input R...

Страница 10: ...Mechanical 3 Both 1 A098 SW Current Trip 0 0 Drive Amps 2 0 1 Amps 0 0 Disabled A099 Process Factor 0 1 999 9 0 1 30 0 A100 Fault Clear 0 2 0 Ready 1 Reset Active Fault 2 Clear Fault Queue 0 A101 Pro...

Страница 11: ...urrent Limit F7 Motor Overload 1 An excessive motor load exists Reduce load so drive output current does not exceed the current set by parameter P033 Motor OL Current F8 Heatsink OvrTmp 1 Check for bl...

Страница 12: ...9 87 4 3 44 168 6 61 2 2 4 9 1 Overall height of drive with IP 30 NEMA 1 UL Type 1 option kit installed 2 Overall height of standard IP 20 Open Type drive Frame 120V AC 1 Phase 240V AC 1 Phase 240V AC...

Отзывы: