6-8
ControlLogix Applications
PowerFlex 700S (32-bit Ref/Fdbk and Datalinks)
Figure 6.11 Module Properties: ControlNet Module Parameters
11.
The
Requested Packet Interval (RPI)
schedules the connection to
move data to or from the adapter at least this often or the connection
will fail with the RPI Not Valid error. Set this value to 5ms or greater
and click
Next>
(
Important:
The RPI time must be set greater than or equal to the
Network Update Time (NUT).
Node configured for:
Input Size
Output Size
Logic Command / Reference and
Logic Status / Feedback only
6
4
plus Datalink A 10
8
plus Datalink B 14
12
plus Datalink C 18
16
plus Datalink D 22
20
20COMM-UM003A-EN-P.book Page 8 Wednesday, November 7, 2001 3:46 PM
Содержание PowerFlex 20-comm-c FRN 1. Series
Страница 6: ...iv Table of Contents Notes 20COMM UM003A EN P book Page iv Wednesday November 7 2001 3 46 PM...
Страница 18: ...1 8 Getting Started 20COMM UM003A EN P book Page 8 Wednesday November 7 2001 3 46 PM...
Страница 34: ...3 10 Configuring the Adapter Notes 20COMM UM003A EN P book Page 10 Wednesday November 7 2001 3 46 PM...
Страница 74: ...5 20 PLC 5C Applications Notes 20COMM UM003A EN P book Page 20 Wednesday November 7 2001 3 46 PM...
Страница 98: ...6 24 ControlLogix Applications Notes 20COMM UM003A EN P book Page 24 Wednesday November 7 2001 3 46 PM...
Страница 114: ...B 6 Adapter Parameters Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Страница 144: ...C 30 ControlNet Objects Notes 20COMM UM003A EN P book Page 30 Wednesday November 7 2001 3 46 PM...
Страница 152: ...Glossary 6 Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Страница 154: ...20COMM UM003A EN P book Page 2 Wednesday November 7 2001 3 46 PM...