B-2
Adapter Parameters
03
[CN Addr Cfg]
Configures the Network if the Node Address
Switches are set to 00 (Updates
Parameter 4 -
[CN Addr Act]
after reset.).
Default:
2
Minimum:
1
Maximum:
99
Type:
Read/Write
Reset Required:
Yes
04
[CN Addr Act]
The actual Network Node Address.
Default:
2
Minimum:
1
Maximum:
99
Type:
Read Only
05
[CN Rate Cfg]
Configures the Network Data Rate (Updates
Parameter 6
-
[CN Rate Act]
after a reset).
Default:
0 = 5 Mbps
Values
0 = 5 Mbps
Type:
Read/Write
Reset Required:
Yes
06
[CN Rate Act]
The actual Network Data Rate.
Default:
0 = 5 Mbps
Values:
0 = 5 Mbps
Type:
Read Only
07
[Ref / Fdbk Size]
The size of the Reference/Feedback (determined
by the drive).
Default:
0 = 16-bit
Values:
0 = 16-bit
1 = 32-bit
Type: Read
Only
08
[Datalink Size]
Size of each Datalink word (determined by the
drive).
Default:
0 = 16-bit
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only
09
[Reset Module]
No action if set to “Ready.” Resets the adapter if
set to “Reset Module.” Restores the adapter to its
factory default settings if set to “Set Defaults.” This
parameter is a command. It will be reset to “0 =
Ready” after the command has been performed.
Default:
0 = Ready
Values
0 = Ready
1 = Reset Module
2 = Set Defaults
Type:
Read/Write
Reset Required:
No
10
[Comm Flt Action]
Sets the action that the adapter will take if it
detects a network failure. This setting is effective
only if I/O that controls the drive is transmitted
through the adapter.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required:
No
Parameter
No. Name and Description
Details
!
ATTENTION:
Risk of injury or equipment damage exists. If the adapter is
transmitting I/O that controls the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting a connected
adapter.
!
ATTENTION:
Risk of injury or equipment damage exists.
Parameter 10 - [Comm
Flt Action]
lets you determine the action of the adapter and connected drive if the
communications are disrupted. By default, this parameter faults the drive. You can
set this parameter so that the drive continues to run. Precautions should be taken
to ensure that the setting of this parameter does not create a risk of injury or
equipment damage.
20COMM-UM003A-EN-P.book Page 2 Wednesday, November 7, 2001 3:46 PM
Содержание PowerFlex 20-comm-c FRN 1. Series
Страница 6: ...iv Table of Contents Notes 20COMM UM003A EN P book Page iv Wednesday November 7 2001 3 46 PM...
Страница 18: ...1 8 Getting Started 20COMM UM003A EN P book Page 8 Wednesday November 7 2001 3 46 PM...
Страница 34: ...3 10 Configuring the Adapter Notes 20COMM UM003A EN P book Page 10 Wednesday November 7 2001 3 46 PM...
Страница 74: ...5 20 PLC 5C Applications Notes 20COMM UM003A EN P book Page 20 Wednesday November 7 2001 3 46 PM...
Страница 98: ...6 24 ControlLogix Applications Notes 20COMM UM003A EN P book Page 24 Wednesday November 7 2001 3 46 PM...
Страница 114: ...B 6 Adapter Parameters Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Страница 144: ...C 30 ControlNet Objects Notes 20COMM UM003A EN P book Page 30 Wednesday November 7 2001 3 46 PM...
Страница 152: ...Glossary 6 Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Страница 154: ...20COMM UM003A EN P book Page 2 Wednesday November 7 2001 3 46 PM...