Configuring the Adapter
3-9
25
[M-S Input]
Configures the I/O Data to be transferred from the
network to the drive.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read/Write
Reset Required:
Yes
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
26
[M-S Output]
Configures the I/O Data to be transferred from the
drive to the network.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read/Write
Reset Required:
Yes
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
27
[Ref Adjust]
Percent scale factor for the Reference from the
Network.
Default:
100.00
Minimum:
0.00
Maximum:
200.00
Type:
Read/Write
Reset Required:
No
Parameter
No. Name and Description
Details
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7
6
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7
6
20COMM-UM003A-EN-P.book Page 9 Wednesday, November 7, 2001 3:46 PM
Содержание PowerFlex 20-comm-c FRN 1. Series
Страница 6: ...iv Table of Contents Notes 20COMM UM003A EN P book Page iv Wednesday November 7 2001 3 46 PM...
Страница 18: ...1 8 Getting Started 20COMM UM003A EN P book Page 8 Wednesday November 7 2001 3 46 PM...
Страница 34: ...3 10 Configuring the Adapter Notes 20COMM UM003A EN P book Page 10 Wednesday November 7 2001 3 46 PM...
Страница 74: ...5 20 PLC 5C Applications Notes 20COMM UM003A EN P book Page 20 Wednesday November 7 2001 3 46 PM...
Страница 98: ...6 24 ControlLogix Applications Notes 20COMM UM003A EN P book Page 24 Wednesday November 7 2001 3 46 PM...
Страница 114: ...B 6 Adapter Parameters Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Страница 144: ...C 30 ControlNet Objects Notes 20COMM UM003A EN P book Page 30 Wednesday November 7 2001 3 46 PM...
Страница 152: ...Glossary 6 Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Страница 154: ...20COMM UM003A EN P book Page 2 Wednesday November 7 2001 3 46 PM...