76
Rockwell Automation Publication 2711P-AP006C-EN-P - November 2018
Chapter 7
Qualify the Runtime Application
8. Configure the driver properties.
ControlNet Communication
See ControlNet Communication for PanelView Plus 7 Terminals user manual,
publication,
, for step-by-step details on how to configure
ControlNet Scheduled and Unscheduled communication with FactoryTalk
View ME software.
Test Run Graphic Displays
FactoryTalk View ME software provides a Test Display mode to test the
animation and assigned tags that are connected to objects in a graphic display.
Any information, warning, or errors are logged to the diagnostic list for your
review.
Test Display mode tests all objects in a display:
• Button objects
• Numeric and string objects to verify that correct values are displayed
• Objects that require user input
• Objects that use animation
For each object tested, review and correct any errors and warnings that are
logged to the diagnostic list. Retest the display object before proceeding to the
next object.
TIP
Remote I/O and DeviceNet communication modules are not supported by
the PanelView Plus 7terminals.
PanelView Plus Compact 400, 600, and 1000 terminals are fixed hardware
configurations that do not support communication modules.
For
On This Terminal
+
Communication Module
Select
DH+™
PanelView Plus 6 (700...1500)
(1)
+
2711P-RN6 or 2711P-RN6K
DH+ (1784-PKTX, 2711P-RN6, 2711P-RN8)
PanelView Plus 400 or 600
+
2711P-RN8
DH+ (1784-PKTX, 2711P-RN6, 2711P-RN8)
DH-485
PanelView Plus 6 (700...1500)
(1)
+
2711P-RN6 or 2711P-RN6K
DH-485 (1784-PKTX, 2711P-RN6)
PanelView Plus 400 or 600
+
2711P-RN3
Serial DH-485 (including 2711P-RN3, 2711P-RN22C)
ControlNet
PanelView Plus 6 (700...1500)
(1)
+
2711P-RN15S or
2711P-RN15SK
ControlNet (1784-PCIC, 1784-PCICS, 2711P-RN15S) or
ControlNet (1784-PKTCS, 2711P-RN15S, 2711P-RN15C)
PanelView Plus 400 or 600
+
2711P-RN15C
ControlNet (1784-PKTCS, 2711P-RN15S, 2711P-RN15C)
(1) Also applies to PanelView Plus 700 to 1500 terminals running FactoryTalk View Machine Edition Firmware Revision 5.1 or earlier.
IMPORTANT
You must be connected to the controller and online before test running the
display or all objects show their error states.
IMPORTANT
In Test Display mode, objects in the display are activated and connected to
assigned tags. Only tags connected to objects in the display work. Links to
other displays or alarms, including data logging, macros, global connections,
and information messages do not work.
Содержание PanelView Plus 7
Страница 1: ...Migrating PanelView Standard Applications to PanelView Plus 7 Migration Guide OriginalInstructions...
Страница 8: ...8 Rockwell Automation Publication2711P AP006C EN P November 2018 Table of Contents Notes...
Страница 64: ...64 Rockwell Automation Publication2711P AP006C EN P November 2018 Chapter 5 Review Object Mapping Notes...
Страница 118: ...118 Rockwell Automation Publication2711P AP006C EN P November 2018 Chapter 9 Optimize Runtime Performance Notes...
Страница 133: ......