Chapter 4
Review the Application Conversion Log
See the FactoryTalk View online help for information on the word length
L parameter.
Table 9 - Conversion Log Messages: Alarms
Message
Description
Bit and LSBit triggered alarms that used a trigger tag
with a bit data type will only be able to trigger a single
alarm after import.
See
for details on alarm
tag data types.
Alarm message Ack option not supported.
In PanelBuilder32 software, the alarm ACK is on an
individual message. FactoryTalk View ME software does
not support individual acknowledgement of alarms. The
alarm Ack is on the triggers.
Alarm List at <location> displays all alarms.
This message describes the type of alarm list.
Alarm List at <location> displays all active alarms.
This message describes the type of alarm list.
Alarm List at <location> will display all alarms that
have come out of alarm.
This message describes the type of alarm list.
Alarm List at <location> does not support displaying
alarms that do not require acknowledgement.
This message describes the type of alarm list.
“Remote Clear All Alarm Tag” alarm control not
supported.
FactoryTalk View ME software does not support this
alarm tag.
“Remote Clear All Alarm Handshake Tag” alarm control
not supported.
FactoryTalk View ME software does not support this
alarm tag.
Tag converted to memory tag, as its address is blank.
The tag was converted to a memory tag because the tag
address was blank in PanelBuilder32 software.
The array size for this tag was invalid and has been set to
the maximum supported size.
The character array size was converted to the maximum
string length of 82.
Bit array tags are not supported. Tag will be converted as
a memory tag.
FactoryTalk View ME software does not support the bit
array data type. Typically, bit arrays were used in
PanelBuilder32 software for addresses less than one
word in length.
In FactoryTalk View ME software, change the tag address
to a full word address. When using non-Remote I/O
addresses, these conversions take place:
• Bit array is converted to an analog, default type
device tag with a word length as opposed to a
memory tag.
• BOOL is converted to a bit tag.
• DINT is converted to an analog, long integer tag.
Содержание PanelView Plus 7
Страница 1: ...Migrating PanelView Standard Applications to PanelView Plus 7 Migration Guide OriginalInstructions...
Страница 8: ...8 Rockwell Automation Publication2711P AP006C EN P November 2018 Table of Contents Notes...
Страница 64: ...64 Rockwell Automation Publication2711P AP006C EN P November 2018 Chapter 5 Review Object Mapping Notes...
Страница 118: ...118 Rockwell Automation Publication2711P AP006C EN P November 2018 Chapter 9 Optimize Runtime Performance Notes...
Страница 133: ......