Kinetix 5700 Regenerative Bus Supply
Connect the Braided Ground Strap
Circuit Breaker/Fuse Specifications
The Kinetix 5700 regenerative bus supplies use internal solid-state motor short-circuit
protection and, when protected by suitable branch circuit protection, are rated for use on a
circuit that can deliver up to 200,000 A (fuses) and 65,000 A (circuit breakers). While circuit
breakers offer some convenience, there are limitations for their use. Circuit breakers do not
handle high-current inrush as well as fuses. Make sure that the selected components are properly
coordinated and meet acceptable codes, which includes requirements for branch circuit
protection. Evaluation of the short-circuit available current is critical and must be kept below the
short-circuit current rating of the circuit breaker.
Item
Description
1
Ground screw (green) 2.0 N•m (17.5 lb•in), max
2
Braided ground strap (customer supplied)
3
Ground grid or power distribution ground
4
Bonded-cabinet ground bus (customer supplied)
MOD
NET
2
1
1
I/O
6
5
10
OK+
OK–
EN–
EN+
Braided Ground Straps
12 mm (0.5 in.) by 0.8 mm (0.03 in.)
Keep straps as short as possible.