Rockwell Automation Publication 2198-IN014A-EN-P - August 2018

Kinetix 5700 Regenerative Bus Supply

Connect the Braided Ground Strap

Circuit Breaker/Fuse Specifications

The Kinetix 5700 regenerative bus supplies use internal solid-state motor short-circuit 
protection and, when protected by suitable branch circuit protection, are rated for use on a 
circuit that can deliver up to 200,000 A (fuses) and 65,000 A (circuit breakers). While circuit 
breakers offer some convenience, there are limitations for their use. Circuit breakers do not 
handle high-current inrush as well as fuses. Make sure that the selected components are properly 
coordinated and meet acceptable codes, which includes requirements for branch circuit 
protection. Evaluation of the short-circuit available current is critical and must be kept below the 
short-circuit current rating of the circuit breaker.

Item

Description

1

Ground screw (green) 2.0 N•m (17.5 lb•in), max

2

Braided ground strap (customer supplied)

3

Ground grid or power distribution ground

4

Bonded-cabinet ground bus (customer supplied)

MOD
NET

2

1

1

I/O

6

5

10

OK+
OK–
EN–
EN+

Braided Ground Straps

12 mm (0.5 in.) by 0.8 mm (0.03 in.)

Keep straps as short as possible.

4

3

2

1

Regenerative Bus Supply

(typical example)

Kinetix 5700 Servo Drives (typical system)

Содержание Kinetix 5700 Series

Страница 1: ...s User Manual publication 2198 UM002 for detailed information on wiring applying power troubleshooting and integration with ControlLogix 5580 controllers with EtherNet IP communication modules or Comp...

Страница 2: ...Wiring plug connector for shunt power RC connections installed on the module These installation instructions publication 2198 IN014 Regenerative Bus Supply Cat No Module Width mm Input Voltage 1 1 Ap...

Страница 3: ...ight specifications These lifting instructions apply to catalog numbers 2198 RP200 2198 RP263 and 2198 RP312 ReadtheLiftingPrecautions Read these precautions before attempting to lift the regenerative...

Страница 4: ...secure the appropriate hardware in the designated lift points as identified in the illustrations ATTENTION To guard against equipment damage verify that the hardware is securely connected to the corre...

Страница 5: ...rt the module to the installation location IMPORTANT When approaching the full upright vertical position the weight can shift and cause the module to swing unexpectedly Control the movement of the mod...

Страница 6: ...s User Manual publication 2198 UM002 to determine the ground jumper setting ATTENTION Risk of equipment damage exists The input power ground configuration must be accurately determined When the ground...

Страница 7: ...nd right of the module is required when mounted adjacent to noise sensitive equipment or clean wire ways The recommended minimum cabinet depth is 300 mm 11 81 in Ground Configuration 1 1 Refer to the...

Страница 8: ...generative bus supply can be mounted on the far right far left or anywhere in between However the far left position is preferred to accommodate the 24V shared bus IMPORTANT Mounttheregenerativebussupp...

Страница 9: ...Hole 345 13 58 Lower Mounting Hole 420 16 54 Lower Mounting Hole 465 18 31 Lower Mounting Hole 27 5 55 0 40 0 55 0 110 55 0 110 110 165 110 110 0 00 IMPORTANT Hole spacing is measured in millimeters a...

Страница 10: ...etix 5700 drive modules Regenerative Bus Supply Cat No A mm in B mm in C mm in D mm in E 1 mm in 1 Maximum distance between lift points 2198 RP088 165 6 50 300 11 8 358 14 1 252 9 92 198 7 80 2198 RP2...

Страница 11: ...ve Bus Supply Features and Indicators on page 12 7 4 12 5 9 8 11 6 6 13 17 16 10 14 3 15 18 19 DC DC DC 24V 24V L3 L2 L1 MOD NET 2 1 1 I O 6 5 10 OK OK EN EN 5700 DC 2 1 15 20 19 20 2198 RP088 and 219...

Страница 12: ...twork status indicator 18 24V control input power CP connector 9 LCD display 19 AC Input power IPD connector 1 1 Connector plug orientation applies to 2198 RP088 and 2198 RP200 modules 2198 RP200 conn...

Страница 13: ...n 2198 UM002 for wiring examples Control Input Power CP Connector Pinout RC Pin Description Signal 2 Active shunt connections DC 1 DC CED Pin Description Signal OK Relay driven contact that provides a...

Страница 14: ...plied 24V supply COM 3 24V current sinking fast input 2 IN2 4 I O common for customer supplied 24V supply COM 5 Chassis ground SHLD 6 24V current sinking fast input 3 IN3 7 I O common for customer sup...

Страница 15: ...7 0 0 28 0 22 0 25 1 9 2 2 DC Bus power Bus bar DC DC N A 1 1 SharedDC bus powerconnectionsarealwaysmadefromdrivetodriveoverthebus barconnectionsystem Theseterminalsdonot receivediscrete wires N A 1 N...

Страница 16: ...dle high current inrush as well as fuses Make sure that the selected components are properly coordinated and meet acceptable codes which includes requirements for branch circuit protection Evaluation...

Страница 17: ...rives User Manual publication 2198 UM002 Bussmann Fuses Cat No Mersen Fuses Cat No Miniature CB Cat No Motor Protection CB Self Protected CMC Cat No Molded Case CB Cat No 2198 RP088 324 506V AC rms LP...

Страница 18: ...t protection must be provided in accordance with the National Electric Code NEC and any additional local codes Leakage current Kinetix 5700 drives produce leakage current in the protective earthing co...

Страница 19: ...IP networking and component servo drive families Kinetix Motion Accessories Specifications Technical Data publication KNX TD004 Provides product specifications for Bulletin 2090 motor and interface ca...

Страница 20: ...elp us serve your documentation needs better If you have any suggestions on how to improve this document complete the HowAre We Doing form at http literature rockwellautomation com idc groups literatu...

Отзывы: