GuardShield™ Type 2 Safety Light Curtain Installation Instructions

                                                     3

Original instructions

Introduction

The GuardShield Type 2 safety light curtain is a general purpose 
presence sensing device, designed for use on hazardous machinery 
providing point of operation, as well as, perimeter and access detection.

It is a self-contained, two box, Type 2 ESPE (Electro Sensitive Protective 
Equipment).

The GuardShield Type 2 is offered in either guard only mode or with a 
restart interlock and EDM.  

Safety Precautions

Principles for Safe Use and Symbols Used

The following instructions are preventive warnings for the proper 
operation of the GuardShield Type 2. These instructions are an essential 
part of the safety precautions and therefore have to be observed at any 
time.

Throughout this manual we use the labels ATTENTION and 
IMPORTANT to alert you to the following:

Failure to observe may result in dangerous operation

ATTENTION: Identifies information about 

practices of circumstances that can lead to personal injury or death, 
property damage, or economic loss.

ATTENTION helps you 

• Identify  a  hazard
• Avoid  a  hazard
• Recognize the consequences

IMPORTANT: Identifies information that is especially important for 
successful application and understanding of the product.

The GuardShield Type 2 may be used in safety applications in which a 
risk analysis according to ANSI TR.3, ANSI/RIA 15.06, pr EN 1050 or 
EN 959-1 have reached Category 2.

Specialist Personnel

The GuardShield Type 2 safety light curtain must be installed, 
commissioned and serviced only by a qualified person. A qualified 
person is defined as a person who:

• Has undergone the appropriate technical training

and

• Who has been instructed by the responsible machine operator in 

the operation of the machine and the currently valid safety 
guidelines

and

• Who has read and has ongoing access to these installation 

instructions

IMPORTANT

These installation instructions are designed 
to address the technical personnel of the 
machine manufacturer and or the installer of 
the safety system regarding the proper 
mounting, configuration, electrical 
installation, commissioning, operation and 
maintenance of the GuardShield Type 2 
safety light curtain. 
These installation instructions do not provide 
instruction for the operation of machinery to 
which the GuardShield Type 2 safety light 
curtain is, or will be, integrated. Only 
qualified personnel should install this 
equipment.

ATTENTION

ATTENTION

Potentially hazardous situation, which, if not 
prevented, might lead to serious or deadly 
injury.
Failure to observe may result in dangerous 
operation.

ATTENTION

The GuardShield Type 2 must not be used 
with machines that cannot be stopped 
electrically in an emergency.
The safety distance between the GuardShield 
Type 2 and a dangerous machine movement 

maintained at all times.
Additional mechanical protective devices have to be 
installed in a way that hazardous machine elements cannot 
be reached without passing through the protective field.
The GuardShield Type 2 has to be installed in a way that 
operators can only operate within the sensing area. 
Improper installation can result in serious injury.
Never connect the outputs to +24V DC. If the outputs are 
connected to +24V DC, they are in ON-state and cannot stop 
hazardous spots at the machine/application.
Never expose the GuardShield Type 2 to flammable or 
explosive gases.
Regular safety inspections are imperative (see maintenance).
Do not repair or modify the GuardShield Type 2. The 
GuardShield Type 2 safety light curtain is not field repairable 
and can only be repaired at the factory. Removal of either of 
the GuardShield Type 2 endcaps will void the warranty terms 
of this product.

Содержание GuardShield Type 2

Страница 1: ...GuardShield Type 2 Safety Light Curtain User Manual...

Страница 2: ...GI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation sales office describes some important differences between...

Страница 3: ...the product as well as the machinery on which the GuardShield Type 2 presence sensing device is installed The installation of GuardShield Type 2 safety light curtains must comply with all applicable...

Страница 4: ...ectrical Installation 10 Connections 10 Typical Wiring Diagram 11 Troubleshooting Guide 12 Checklist 14 Safety Instructions Maintenance 14 Daily Inspection 14 Six month Inspection 15 Cleaning 15 Date...

Страница 5: ...tion of the machine and the currently valid safety guidelines and Who has read and has ongoing access to these installation instructions IMPORTANT These installation instructions are designed to addre...

Страница 6: ...rized personnel and must be recorded and documented to ensure that the tests can be reconstructed and retraced at any time The installation instructions must be made available to the user of the machi...

Страница 7: ...required Resetting of the system is accomplished through a momentary N O push button or key switch The restart interlock mode is indicated by the illumination of a yellow LED on the GuardShield Type...

Страница 8: ...t of operation hazard from rest NOTE ANSI B11 19 1990 E4 2 3 3 5 states The value of the hand speed constant K has been determined by various studies and although these studies indicate speeds of 63 i...

Страница 9: ...0 0 32 8 30 14 640 mm 25 1 in Example In opto electronic safeguarding such as with a perpendicular safety light curtain applications with object sensitivity effective resolution less than 2 5 inches t...

Страница 10: ...tem powers up and goes to the ON state alignment indicator is OFF An external laser 440L ALAT and mounting bracket 440L AF6109 is offered as an accessory for aligning the GuardShield Type 2 The GuardS...

Страница 11: ...le brackets attached to the endcaps of both transmitter and receiver It may be necessary to use additional brackets to mount the GuardShield Type 2 at a proper safety distance from the machinery hazar...

Страница 12: ...e reset button restart button Connections mm in Cables Connectors The GuardShield Type 2 transmitter connector is a four pin DC micro connector offered in cable lengths from 2 to 30 meters The GuardSh...

Страница 13: ...ing Diagram To MSR127 Safety Relay Module M 24VDC 24V Ground SENDER OSSD 1 OSSD 2 RECEIVER K1 Bulletin 100S Safety Contactors or 700S Safety Relays K2 L1 L3 L2 Gray Pink Green Blue Blue Yellow Brown B...

Страница 14: ...al fault transmitter Check connections transmitter receiver Exchange transmitter 8 External fault Check connections of OSSD outputs for short circuit against 24V DC and GND cable connected devices Rep...

Страница 15: ...OFF ON OFF ON ON 4 ON OFF OFF ON ON ON 5 ON OFF OFF OFF ON OFF 6 FLASH OFF OFF OFF ON ON 7 ON OFF OFF OFF FLASH ON 8 FLASH OFF ON OFF ON ON 9 FLASH OFF OFF ON ON ON Condition No Description 1 Guard on...

Страница 16: ...onal power supply 9 If two or more GuardShield Type 2 are to be used make sure that each system is properly installed in order to avoid optical interference 10 Two seconds after switching on the syste...

Страница 17: ...than the calculated value 5 Cables and plugs of the GuardShield Type 2 are in flawless condition 6 Mounting brackets caps and cables are tightly secured Transmitter Receiver Location of Manufacture Y...

Страница 18: ...s OSSDs Auxiliary Output 2 solid state outputs max switching capacity 500 mA short circuit protected max residual voltage 2V excl voltage drop through cables Solid state output max power consumption 5...

Страница 19: ...0YD 440L R2K 0800YD 30 1 18 40 800 31 49 2 5 5 5 440L P2K 0960YD 440L T2KA0960YD 440L R2K 0960YD 30 1 18 48 960 37 79 2 9 6 4 440L P2K 1120YD 440L T2KA1120YD 440L R2K 1120YD 30 1 18 56 1120 44 09 3 4...

Страница 20: ...480 0 5 605 641 1 5 440L P2K 0640YD 640 0 5 765 801 1 5 440L P2K 0800YD 800 0 5 925 961 1 5 440L P2K 0960YD 960 0 5 1085 1121 1 5 440L P2K 1120YD 1120 0 5 1245 1281 1 8 440L P2K 1280YD 1280 0 5 1405 1...

Страница 21: ...L AF6108 Power supply Output 24V DC 3 Amps 72 W 1606 XLP72E Laser alignment tool 440L ALAT GuardShield Type 2 laser alignment tool bracket 440L AF6109 Mounting stand 440L AMSTD Vertical shock mount ki...

Страница 22: ...146 1090 1122 1190 1296 1240 1272 1340 1446 1390 1422 1490 1596 1540 1572 1640 1746 1690 1722 1790 1896 1840 1872 1940 Series Z A A 120 8 X 13 Z 164 6 45 35 1 37 13 3 0 52 54 2 12 Section A 44 4 174 7...

Страница 23: ...40L P2K 0480YD 440L AM0750600 440L AM1250600 440L P2K 0640YD 440L AM0750750 440L AM1250750 440L P2K 0800YD 440L AM0750900 440L AM1250900 440L P2K 0960YD 440L AM0751050 440L AM1251050 440L P2K 1120YD 4...

Страница 24: ...Female Cordset 20 65 6 889D F8AB 30 8 pin DC Micro Straight Female Cordset 30 98 4 889D R8AB 2 8 pin 8 wire DC Micro Right Angle Female Cordset 2 6 5 889D R8AB 5 8 pin 8 wire DC Micro Right Angle Fema...

Страница 25: ...ied EN 55022 1998 A1 2000 A2 2003 Information technology equipment Radio disturbance characteristics Limits and methods of measurement EN 61496 1 2004 A1 2008 Safety of machinery Electro sensitive pro...

Страница 26: ...Shield safety light curtains 2 Light Curtain Type P Transmitter receiver pair R Receiver T Transmitter 3 Optoelectronic Safety Type 2 Type 2 4 Beam Resolution K 30mm 5 Electronic Unit Type A Guard Onl...

Страница 27: ...GuardShield Type 2 Safety Light Curtain Installation Instructions 25 R Original instructions...

Страница 28: ...Rockwell Automation Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong...

Отзывы: