GuardShield™ Type 2 Safety Light Curtain Installation Instructions

16         

R

Original instructions

Technical Specifications

Light Beams

8 – 88

Protective Field

160…1760 mm (6.3…69.29 in.) in 160 mm (6.3 in.) increments

Resolution

30 mm (1.18 in.)

Range

30 mm (1.18 in.); 0.3…18.0 m (0.98…59.0 ft)

Response Time

OSSD – ON to OFF: (Reaction times); 20…25 ms

Power Supply

24V DC +/-20%; Power supply must meet the requirements of IEC 60204-1 and IEC 61496-1.

Power Consumption

400 mA max. (unloaded)

 

IR Transmitter

Infrared LED (wave length 870 nm)

Aperture Angle

Within ± 5.0° for transmitter and receiver

Operating Condition

IR transmitter ON

Functions

Guard Only:

On/Off operation with clear/obstructed detection area

Start Interlock:

Interlock at start up—Reset by actuation of momentary N.O. pushbutton switch (or
interruption/restoration of light curtain)

Restart Interlock:

Interlock at interruption of sensing field—Reset by actuation of momentary N.O. 
pushbutton switch

Relay Monitoring:

Monitoring a switch contact of the installation

Test Function:

Triggering of system test via external switch 

Inputs Transmitter

Machine Test Signal Minimum duration 100 ms

Voltage level for Logic 0:

0…5V DC

Voltage level for Logic Hi 1:

 > 16V DC

Inputs Receiver

Start/Restart Interlock

Logic Lo
Minimum duration 100 ms; maximum duration 900 ms
Voltage level for Logic Lo 0:

0…5V DC

Voltage level for Logic Hi 1:

> 16V DC

MPCE 300 ms after activation of OSSD

Voltage level for Logic 0:

0…5V DC

Voltage level for Logic Hi 1:

> 16V DC

Outputs:

Safety Outputs (OSSDs)

Auxiliary Output

2 solid state outputs, max. switching capacity 500 mA,

 

short circuit protected, max. residual voltage

 

2V (excl. voltage drop 

through cables)
Solid state output, max. power consumption 500 mA, max. residual voltage 2V—nonsafety output

Status Indicators Receiver

ON-state

OFF-state

Alignment

Interlock

Constant ON when system is in ON-state (green LED) 
Constant ON when system is in OFF-state (red LED)

•  Lights up at interruption of protective field or if fault occurs

Lights up, if input signal is too weak (amber LED)
Lights up when light curtain is in start or restart interlock mode (yellow LED)

Status Indicators Sender

Power ON

Emitting

Lights up, when voltage is on (amber LED)
Constant ON when transmitter is active (yellow LED)

QD Connectors

Transmitter: M12 plug 4 pin; receiver: M12 plug 8 pin

Cable Length

Maximum 30 m (100 ft)

Ambient Temperature

During operation: –10…55°C (14…131°F); For storage: –25…75°C (-13…167°F)

Humidity of the Air 

Up to 95%

 

(without condensation) between 20°C and 55°C (68°F and 131°F)

Enclosure Rating

IP65

Vibration Resistance

Per IEC 61496-1, IEC 60068-2-6 Frequency 10…55 Hz Amplitude 0.35 mm

Shock

Per IEC 61496-1, IEC 60068-2-29 Acceleration 10 g, Duration 16 ms

Material

Housing: Aluminum; Cover: PMMA (acrylic)

Dimensions (cross section)

Approx. 40 x 50mm (1.57 x 1.96 in.) 

Accessories Included

Test rod, mounting brackets, operating instructions

Approvals

IEC 61496 Parts 1and 2, UL 61496 Parts 1 and 2, UL 1998

Safety Classification

Type 2 per EN/IEC 61496, Category 2 EN/ISO 13849, SIL 2, IEC 61508, SIL CL2, EN 62061, PLd, EN/ISO 13849

PFHd (mean probability of a dangerous failure/hr

Standalone sys.: 9.51 x 10

-9

T

M

 (mission time)

20 years (EN ISO 13849)

Transmitter Wave Length

870 nm

Содержание GuardShield Type 2

Страница 1: ...GuardShield Type 2 Safety Light Curtain User Manual...

Страница 2: ...GI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation sales office describes some important differences between...

Страница 3: ...the product as well as the machinery on which the GuardShield Type 2 presence sensing device is installed The installation of GuardShield Type 2 safety light curtains must comply with all applicable...

Страница 4: ...ectrical Installation 10 Connections 10 Typical Wiring Diagram 11 Troubleshooting Guide 12 Checklist 14 Safety Instructions Maintenance 14 Daily Inspection 14 Six month Inspection 15 Cleaning 15 Date...

Страница 5: ...tion of the machine and the currently valid safety guidelines and Who has read and has ongoing access to these installation instructions IMPORTANT These installation instructions are designed to addre...

Страница 6: ...rized personnel and must be recorded and documented to ensure that the tests can be reconstructed and retraced at any time The installation instructions must be made available to the user of the machi...

Страница 7: ...required Resetting of the system is accomplished through a momentary N O push button or key switch The restart interlock mode is indicated by the illumination of a yellow LED on the GuardShield Type...

Страница 8: ...t of operation hazard from rest NOTE ANSI B11 19 1990 E4 2 3 3 5 states The value of the hand speed constant K has been determined by various studies and although these studies indicate speeds of 63 i...

Страница 9: ...0 0 32 8 30 14 640 mm 25 1 in Example In opto electronic safeguarding such as with a perpendicular safety light curtain applications with object sensitivity effective resolution less than 2 5 inches t...

Страница 10: ...tem powers up and goes to the ON state alignment indicator is OFF An external laser 440L ALAT and mounting bracket 440L AF6109 is offered as an accessory for aligning the GuardShield Type 2 The GuardS...

Страница 11: ...le brackets attached to the endcaps of both transmitter and receiver It may be necessary to use additional brackets to mount the GuardShield Type 2 at a proper safety distance from the machinery hazar...

Страница 12: ...e reset button restart button Connections mm in Cables Connectors The GuardShield Type 2 transmitter connector is a four pin DC micro connector offered in cable lengths from 2 to 30 meters The GuardSh...

Страница 13: ...ing Diagram To MSR127 Safety Relay Module M 24VDC 24V Ground SENDER OSSD 1 OSSD 2 RECEIVER K1 Bulletin 100S Safety Contactors or 700S Safety Relays K2 L1 L3 L2 Gray Pink Green Blue Blue Yellow Brown B...

Страница 14: ...al fault transmitter Check connections transmitter receiver Exchange transmitter 8 External fault Check connections of OSSD outputs for short circuit against 24V DC and GND cable connected devices Rep...

Страница 15: ...OFF ON OFF ON ON 4 ON OFF OFF ON ON ON 5 ON OFF OFF OFF ON OFF 6 FLASH OFF OFF OFF ON ON 7 ON OFF OFF OFF FLASH ON 8 FLASH OFF ON OFF ON ON 9 FLASH OFF OFF ON ON ON Condition No Description 1 Guard on...

Страница 16: ...onal power supply 9 If two or more GuardShield Type 2 are to be used make sure that each system is properly installed in order to avoid optical interference 10 Two seconds after switching on the syste...

Страница 17: ...than the calculated value 5 Cables and plugs of the GuardShield Type 2 are in flawless condition 6 Mounting brackets caps and cables are tightly secured Transmitter Receiver Location of Manufacture Y...

Страница 18: ...s OSSDs Auxiliary Output 2 solid state outputs max switching capacity 500 mA short circuit protected max residual voltage 2V excl voltage drop through cables Solid state output max power consumption 5...

Страница 19: ...0YD 440L R2K 0800YD 30 1 18 40 800 31 49 2 5 5 5 440L P2K 0960YD 440L T2KA0960YD 440L R2K 0960YD 30 1 18 48 960 37 79 2 9 6 4 440L P2K 1120YD 440L T2KA1120YD 440L R2K 1120YD 30 1 18 56 1120 44 09 3 4...

Страница 20: ...480 0 5 605 641 1 5 440L P2K 0640YD 640 0 5 765 801 1 5 440L P2K 0800YD 800 0 5 925 961 1 5 440L P2K 0960YD 960 0 5 1085 1121 1 5 440L P2K 1120YD 1120 0 5 1245 1281 1 8 440L P2K 1280YD 1280 0 5 1405 1...

Страница 21: ...L AF6108 Power supply Output 24V DC 3 Amps 72 W 1606 XLP72E Laser alignment tool 440L ALAT GuardShield Type 2 laser alignment tool bracket 440L AF6109 Mounting stand 440L AMSTD Vertical shock mount ki...

Страница 22: ...146 1090 1122 1190 1296 1240 1272 1340 1446 1390 1422 1490 1596 1540 1572 1640 1746 1690 1722 1790 1896 1840 1872 1940 Series Z A A 120 8 X 13 Z 164 6 45 35 1 37 13 3 0 52 54 2 12 Section A 44 4 174 7...

Страница 23: ...40L P2K 0480YD 440L AM0750600 440L AM1250600 440L P2K 0640YD 440L AM0750750 440L AM1250750 440L P2K 0800YD 440L AM0750900 440L AM1250900 440L P2K 0960YD 440L AM0751050 440L AM1251050 440L P2K 1120YD 4...

Страница 24: ...Female Cordset 20 65 6 889D F8AB 30 8 pin DC Micro Straight Female Cordset 30 98 4 889D R8AB 2 8 pin 8 wire DC Micro Right Angle Female Cordset 2 6 5 889D R8AB 5 8 pin 8 wire DC Micro Right Angle Fema...

Страница 25: ...ied EN 55022 1998 A1 2000 A2 2003 Information technology equipment Radio disturbance characteristics Limits and methods of measurement EN 61496 1 2004 A1 2008 Safety of machinery Electro sensitive pro...

Страница 26: ...Shield safety light curtains 2 Light Curtain Type P Transmitter receiver pair R Receiver T Transmitter 3 Optoelectronic Safety Type 2 Type 2 4 Beam Resolution K 30mm 5 Electronic Unit Type A Guard Onl...

Страница 27: ...GuardShield Type 2 Safety Light Curtain Installation Instructions 25 R Original instructions...

Страница 28: ...Rockwell Automation Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong...

Отзывы: