Rockwell Automation Publication 440R-UM013E-EN-P - March 2017
19
Power, Ground, and Wire
Chapter 3
lists the terminal functions. Many of the terminals perform common
functions on multiple relays.
Table 1 - Terminal Assignments and Functions
Ground the Relay
There are no special grounding requirements. Terminal A2 must be connected
to the common of a 24V supply.
Terminal
Function
Applies To
A1
+24V Supply (+10%, -15%)
All
A2
24V Common
All
S11
Pulse Test Output for Channel 1
CI, DI, DIS, and SI
S21
Pulse Test Output for Channel 2
CI, DI, DIS, and SI
S12
Safety Input for IN1 Channel 1
CI, DI, DIS, and SI
S22
Safety Input for IN1 Channel 2
CI, DI, DIS, and SI
S32
Safety Input for IN2 Channel 1
DI and DIS
S34
Reset Input
CI, DI, DIS, and SI
S42
Safety Input for IN2 Channel 2
DI and DIS
Y32
Auxiliary Non-safety Output
CI, DI, DIS, and SI
X32
Auxiliary Non-safety Output
EM and EMD
B1
Jog Input
EMD
B2
Retrigger Input
EMD
L11
Single Wire Safety Output
All
L12
Single Wire Safety Input
DI, DIS, EM, and EMD
13/14, 23/24
Safety Outputs - electromechanical relay
CI, DI, EM, and SI
33/34, 43/44
Safety Outputs - electromechanical relay
EM
14, 24
Safety Outputs - OSSD
DIS
34, 44
Safety Outputs - OSSD for capacitive loads
DIS
17/18, 27/28, 37/38, 47/48
Safety Outputs, Delayed - electromechanical relay
EMD
Содержание Guardmaster
Страница 12: ...12 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 1 Overview Notes...
Страница 16: ...16 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 2 Installation Notes...
Страница 34: ...34 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 3 Power Ground and Wire Notes...
Страница 40: ...40 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 4 Configuration Notes...
Страница 50: ...50 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 7 EMD Safety Relay Timing Functions Notes...
Страница 99: ......