Publication 1794-RM001G-EN-P - December 2011
3-6
FLEX I/O Modules
Users can also wire a standard digital output module in series with an isolated
relay output module in series with a critical actuator. In the event that a failure
is detected, the output from both output modules must be set to OFF to
guarantee the Output Loads de-energize. This is shown in Figure 3.6.
Figure 3.6 ControlLogix/FLEX I/O Standard Output Module Wiring With an Isolated
Relay Module
1 2
3 4 5
6 7
8 9 10 11 12 13 14 15
0
24VDC SINK INPUT
1794-IB16
1 2
3 4 5
6 7
8 9 10 11 12 13 14 15
0
24VDC SOURCE OUTPUT
1794-OB16
1 2
3 4 5
6 7
8 9 10 11 12 13 14 15
0
24VDC SOURCE OUTPUT
1794-OB16
Isolated Relay
Output Module
43364
Standard Digital
Input Module
Standard Digital
Output Module
+24V
COM
Wire output point
to input point to
verify the correct
state of the output
Output
Output
Actuator
+24V
COM
Note 1: An external relay can be replaced with an isolated
relay module which is mounted in another FLEX I/O rail.
Содержание FlexLogix 1794
Страница 1: ...FLEXI OSystemwithControlLogixforSIL2 Catalog Number Bulletin 1794 Reference Manual AB Drives ...
Страница 18: ...Publication 1794 RM001G EN P December 2011 1 14 SIL Policy Notes ...
Страница 22: ...Publication 1794 RM001G EN P December 2011 2 4 ControlLogix Communications ...
Страница 42: ...Publication 1794 RM001G EN P December 2011 3 20 FLEX I O Modules Notes ...
Страница 44: ...Publication 1794 RM001G EN P December 2011 4 2 General Requirements for Application Software Notes ...
Страница 46: ...Publication 1794 RM001G EN P December 2011 5 2 Technical SIL2 Requirements for the Application Program Notes ...
Страница 56: ...Publication 1794 RM001G EN P December 2011 A 10 Failure Estimates Notes ...
Страница 59: ...AB Drives ...