10
FlexLogix Controller System
Publication 1794-IN002F-EN-P - October 2002
4.
Make sure power is not applied to the power supply. Connect the
power supply to the controller. This diagram and its related instructions
describe a 1794-PS13 power supply.
a. C24V dc input to the top of the controller connector, terminal
A
,
to the bottom, left power connector, terminal
G
.
b. Connect -24V common to top controller connector, terminal
B
, to the top,
left power connector, terminal
E
.
c. Use connections
C
and
D
on the controller and connection
F
and
H
on
the power supply to pass 24V dc power and common to the next module
in the series, if required.
Use the screw-terminal connector plug that comes with the controller to
meet the requirements for installations in Class I, Division 2 locations.
+
+
A
B
C
D
F
E
H
G
_
_