The following information applies when 
operating this equipment in hazardous 
locations:

Informations sur l’utilisation de cet équipement 
en environnements dangereux:

Products marked “CL I, DIV 2, GP A, B, C, D” are 
suitable for use in Class I Division 2 Groups A, B, C, 
D, Hazardous Locations and nonhazardous locations 
only. Each product is supplied with markings on the 
rating nameplate indicating the hazardous location 
temperature code. When combining products within 
a system, the most adverse temperature code (lowest 
“T” number) may be used to help determine the 
overall temperature code of the system. 
Combinations of equipment in your system are 
subject to investigation by the local Authority Having 
Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu’à une utilisation en environnements 
de Classe I Division 2 Groupes A, B, C, D dangereux 
et non dangereux. Chaque produit est livré avec des 
marquages sur sa plaque d’identification qui 
indiquent le code de température pour les 
environnements dangereux. Lorsque plusieurs 
produits sont combinés dans un système, le code de 
température le plus défavorable (code de 
température le plus faible) peut être utilisé pour 
déterminer le code de température global du 
système. Les combinaisons d’équipements dans le 
système sont sujettes à inspection par les autorités 
locales qualifiées au moment de l’installation.

WARNING

!

EXPLOSION HAZARD

·

Do not disconnect 
equipment unless 
power has been 
removed or the area is 
known to be 
nonhazardous. 

·

Do not disconnect 
connections to this 
equipment unless 
power has been 
removed or the area is 
known to be 
nonhazardous. Secure 
any external 
connections that mate 
to this equipment by 
using screws, sliding 
latches, threaded 
connectors, or other 
means provided with 
this product.

·

Substitution of 
components may impair 
suitability for Class I, 
Division 2.

·

If this product contains 
batteries, they must 
only be changed in an 
area known to be 
nonhazardous.

AVERTISSEMENT

!

RISQUE D’EXPLOSION

·

Couper le courant ou 
s’assurer que 
l’environnement est 
classé non dangereux 
avant de débrancher 
l'équipement.

·

Couper le courant ou 
s'assurer que 
l’environnement est 
classé non dangereux 
avant de débrancher les 
connecteurs. Fixer tous 
les connecteurs 
externes reliés à cet 
équipement à l'aide de 
vis, loquets coulissants, 
connecteurs filetés ou 
autres moyens fournis 
avec ce produit.

·

La substitution de 
composants peut rendre 
cet équipement 
inadapté à une 
utilisation en 
environnement de 
Classe I, Division 2.

·

S’assurer que 
l’environnement est 
classé non dangereux 
avant de changer les 
piles.

Содержание FlexLogix 1794-FLA

Страница 1: ...ust be upgraded to match the version of RSLogix 5000 that you are using e g if you are using RSLogix 5000 V11 you must upgrade your FlexLogix controller firmware to revision 11 x before using it For m...

Страница 2: ...the examples shown in this publication Allen Bradley publication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Au...

Страница 3: ...ucted as well as radiated disturbance This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions tha...

Страница 4: ...nd affect normal operation Follow these guidelines when you handle this equipment Touch a grounded object to discharge potential static Wear an approved grounding wriststrap Do not touch connectors or...

Страница 5: ...d splitting I O across DIN rails see the FLEX I O Product Data publication 1794 2 1 Use DIN rail locks A B catalog number 1492 EA35 to meet the shock and vibrations specifications listed on 21 A pair...

Страница 6: ...on two 1492 EA35 DIN rail locks The system components you have depend on your application You might have FlexLogix System Component Description 1788 CNC CNCR for ControlNet communications 1788 CNF CNF...

Страница 7: ...r safety information on the handling of lithium batteries including the handling and disposal of leaking batteries see Guidelines for Handling Lithium Batteries publication AG 5 4 Store batteries in a...

Страница 8: ...per grounding Do not over tighten the screws The maximum torque for the card screws is 4 8 5 2 inch pounds 5 After the controller is installed see 9 you can connect the network cable Removing a commun...

Страница 9: ...troller onto the DIN rail Release the locking tabs to lock the controller in place If necessary push up on the locking tabs to lock 3 Ground the controller The DIN rail and the common conductive surfa...

Страница 10: ...connector terminal A to the bottom left power connector terminal G b Connect 24V common to top controller connector terminal B to the top left power connector terminal E c Use connections C and D on t...

Страница 11: ...l an I O module see the installation instructions for that module Removing the controller If you need to remove the controller follow these steps 1 Turn off power to the controller 2 Disconnect all ca...

Страница 12: ...apter onto the DIN rail If the adapter does not lock in place use a screwdriver or similar device to move the locking tab down while pressing the adapter onto the DIN rail Release the locking tab to l...

Страница 13: ...r connector terminal B to the top left power connector terminal E c Use connections C and D on the adapter and connection F and H on the power supply to pass 24V dc power and common to the next module...

Страница 14: ...rconnect Cable Installation Instructions publication 1794 5 12 Removing the extended local adapter If you need to remove the adapter follow these steps 1 Turn off power to the adapter 2 Disconnect all...

Страница 15: ...rial port 1 Determine whether you need an optical isolator If you connect the controller to a device outside of the system s enclosure consider installing an isolator between the controller and device...

Страница 16: ...r right angle connector housing than the 1756 CP3 cable yes The 1761 CBL AP00 cable right angle connector to controller or the 1761 CBL PM02 cable straight connector to the controller attaches the con...

Страница 17: ...r WARNING If you connect or disconnect the serial cable with power applied to this module or the serial device on the other end of the cable an electrical arc can occur This could cause an explosion i...

Страница 18: ...turn outputs to the state commanded by the logic of the project YES YES turn outputs to their configured state for Program mode YES YES YES execute scan tasks YES YES YES change the mode of the contro...

Страница 19: ...troller requires a FLASH upgrade to the proper firmware revision see below after the controller is operating recoverable fault red controller faulted clear faults clear memory or replace the controlle...

Страница 20: ...hoose OK 7 Select the revision level to which you want to update the controller and choose Next 8 To start the update of the controller choose Finish and then Yes After the controller is updated the s...

Страница 21: ...0068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 0 to 60 C 32 to 140 F storage temperature IEC 60068 2 1 Test Ab Un packaged Non...

Страница 22: ...E3 cable 3 feet category 3 2 DIN rail steel 35 x 7 55mm DIN rail A B part number 199 DR1 46277 3 EN 50022 Certifications when product is marked UL UL Listed Industrial Control Equipment CSA CSA Certif...

Страница 23: ...4 9mm 3 34in 50 43mm 1 99in 121 97mm 4 81in 182 96mm 7 203in 88 57mm 3 49in 105 96mm 4 17in 101 49mm 3 99in 6 4mm 0 25in 104 57mm 4 12in 87 24mm 3 43in 92 96mm 3 66in 88 57mm 3 49in 80 14mm 3 16in 101...

Страница 24: ...r 2002 FlexLogix Extended Local I O Adapter Approximate Mounting Dimensions Approximate Mounting Clearance 94mm 3 7in 69mm 2 72in 117 12mm 4 61in 88 94mm 3 5in 81 06mm 3 19in 25 4 mm 1 in 25 4 mm 1 in...

Страница 25: ...pment shall be used within its specified ratings defined by Allen Bradley Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40 when applie...

Страница 26: ...ode de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les combinaisons d quipements dans le syst me sont sujettes inspection par les autorit s loca...

Страница 27: ...utomation Wiring and Grounding Guidelines 1770 4 1 Flex 1794 PS3 Power Supply Installation Instructions 1794 5 71 Flex 1794 PS13 Power Supply Installation Instructions 1794 5 69 Flex I O Terminal Base...

Страница 28: ...Publication 1794 IN002F EN P October 2002 PN 957689 50 Supersedes Publication 1794 IN002E EN P November 2001 Copyright 2002 Rockwell Automation All rights reserved Printed in the U S A...

Отзывы: