12
FLEX I/O Digital Input and Output Modules w/ Diagnostics
Publication 1794-IN096C-EN-P - August 2015
Diagnostics
(See configuration information below for location of diagnostic bits.)
Note:
Each unused
sensor port requires a dummy resistor to mask the channel diagnostic function.
Diagnostic Functions for the 1794-IB16D
Ext.
Power
Wiring
Input
Status
Channe
l LED
Status
Open
Wire
Error
Bit
Short
Error
Bit
Rev.
Error
Bit
Module
Error
Bit/LED
OFF
Open
Off
Off
0
0
0
0/OFF
On
Off
0
0
0
0/OFF
Short
Off
Off
0
0
0
0/OFF
On
Off
0
0
0
0/OFF
Normal
Off
Off
0
0
0
0/OFF
On
Off
0
0
0
0/OFF
ON
Open
Off
RED
1
0
0
1/RED
On
RED/YEL
1
0
0
1/RED
Short
Off
RED
0
1
0
1/RED
On
RED/YEL
0
1
0
1/RED
Normal
Off
Off
0
0
0
0/OFF
On
YEL
0
0
0
0/OFF
REV
Open
Off
Off
0
0
1
1/RED
On
Off
0
0
1
1/RED
Short
Off
Off
0
0
1
1/RED
On
Off
0
0
1
1/RED
Normal
Off
Off
0
0
1
1/RED
On
Off
0
0
1
1/RED
The module monitors each sensor-power port for current and voltage. It turns on the channel red LED
and sets (1) the error bit when 1) the module detects a short circuit (no voltage at the sensor-port), and 2)