Produce and Consume Tags (interlock controllers)
Chapter 5
7.
From the Tag Properties dialog box, complete these fields:
•
•
From the Type pull-down menu, choose Consumed.
In the Data Type field, type a data type that the controller can produce.
A controller cannot produce a tag by using the MSG or INT data types.
8.
Click Connection.
9.
From the Consumed Tag Connection dialog box, complete these fields:
•
From the Producer pull-down menu, choose Producing_controller.
This menu contains all possible paths to previously configured
•
controllers in the I/O tree.
In the Remote Data field, type the name of the produced tag in the
•
producing controller.
In the RPI field, enter the rate at which the tag will be produced.
10.
Click OK.
11.
Use RSNetWorx for ControlNet software to schedule the network.