ControlNet Modular Repeater Adapter
21
Rockwell Automation Publication 1786-IN013F-EN-P - April 2011
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 and 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on power ports
±4 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth
(CM) on power ports
±2 kV line-earth (CM) on communication
ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz
Certifications
(1)
- 1786-RPA/B
Certification
(2)
1786-RPA/B
UL
UL Listed Industrial Control Equipment.
See UL File E65584.
CSA
CSA Certified Process Control Equipment.
See CSA File LR54689C.
CSA Certified Process Control Equipment for
Class I, Division 2 Group A, B, C, D
Hazardous Locations.
See CSA File LR69960C.
FM
FM Approved Equipment for use in Class I
Division 2 Group A,B,C,D Hazardous
Locations.
Environmental Specifications - 1786-RPA/B
Attribute
1786-RPA/B