Allen-Bradley ControlLogix DeviceNet Скачать руководство пользователя страница 7

Rockwell Automation Publication 1756-IN065A-EN-P - September 2017

7

ControlLogix DeviceNet Scanner Module

Switch Settings 

Set the Rotary Switches

Use the node address rotary switches to change the DeviceNet node 
address for the 1756-DNB scanner.

1. If the module is removed from the chassis, be sure that power is 

removed or the area is nonhazardous before proceeding.

2. Move the rotary switches to the desired position.

3. If necessary, reinstall the module into the chassis.

Use RSNetWorx for DeviceNet Software

Follow this procedure to use RSNetWorx for DeviceNet software to set 
the node address.

For more information, see DeviceNet Modules in Logix5000 Control 
Systems, publication 

DNET-UM004

.

1. In RSNetWorx for DeviceNet software, select the 1756-DNB 

scanner.

2. Click Tools > Node Commissioning.

3. Browse to the DeviceNet network for the 1756-DNB scanner 

you want to commission.

4. Select the 1756-DNB scanner you want to commission.

5. In the Address field, select the node address.

6. Click Apply.

Restore the Factory Default Settings

The out-of-box reset clears the scanlist (including ADR configuration 
recovery files) and return all software setting attributes to their default 
values.

Follow this procedure to restore the factory default communication 
rate and node address.

1. Set the switches to 888.

2. Restore power to the module.

When the out-of-box reset is complete, the alphanumeric 
display repeatedly scrolls the message Reset Complete - 
Change Switch Settings. During this time, the module does 
not respond to communication from any port (including the 
backplane, DeviceNet connector, or USB port).

3. After the module resets, perform the following steps.

a. Set the switches to the desired position.

b. Restore power to the module.

Install the Module in the Chassis

Switch Settings

Switch Setting

Node Address

0...63

DeviceNet node address 00...63

88

When all three switches are set to 8, resets the 1756-DNB scanner to 
factory default settings. Do not use for normal operation.

All other values

Select the node address with RSNetWorx for DeviceNet software.

IMPORTANT

For ease of access, remove the module from the chassis 
before proceeding.

DeviceNet Node Address Rotary Switches

Top of Module

Least Significant Digit Switch

Most Significant Digit Switch

Front of 
Module

IMPORTANT

Do not use the 888 switch setting during normal module 
operation.

31715-M

Align the circuit board with top
bottom guides in the chassis.

1

Slide the module into the 
chassis. Make sure that the 
module backplane connector 
properly connects to the chassis 
backplane.

2

The module is properly installed when it is 
flush with the power supply or other 
installed modules.

3

Circuit Board

Содержание ControlLogix DeviceNet

Страница 1: ...756 DNB 1756 DNBK ControlLogix DeviceNet scanners are devices that are used with various programmable controllers on the DeviceNet network Topic Page About the Module 5 Determine Module Slot Location 5 Change Module Settings 5 Install the Module in the Chassis 7 Specifications 9 Additional Resources 10 ...

Страница 2: ...code de pratique en vigueur Si cet équipement est utilisé d une façon qui n a pas été définie par le fabricant la protection fournie par l équipement peut être compromise 주의 본 제품 설치 설정 작동 또는 유지 보수하기 전에 본 문서를 포함하여 설치 설정 및 작동에 관한 참고 자료 섹션의 문서들을 반드시 읽고 숙지하 십시오 사용자는 모든 관련 규정 법규 및 표준에서 요구하는 사항에 대해 반드시 설치 및 배선 지침을 숙지해야 합니다 설치 조정 가동 사용 조립 분해 유지보수 등 모든 작업은 관련 규정에 따라 적절한 교육을 받은 사용자를 통해서만 수행해야 합니다 본 장비를 제조사...

Страница 3: ...itution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I Division 2 S assurer que l environnement est classé non dangereux avant de changer les piles European Hazardous Location Approval The following applies to products marked II 3 G Are Equipment Group II Equipment Category 3 and comply withthe Essential Health and Safety Requirements relating to t...

Страница 4: ...that can affect module operation Waste Electrical and Electronic Equipment WEEE Attheendofitslife thisequipmentshouldbecollectedseparatelyfromany unsorted municipal waste Prevent Electrostatic Discharge ATTENTION Thisequipmentissensitivetoelectrostaticdischarge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment Touch a grounded object...

Страница 5: ...ng in a 4 slot chassis Slot 0 is the first slot and is always the leftmost slot in the chassis ChangeModuleSettings The module ships with these settings Factory Setting Values Factory Settings Value Rotary switches 999 Communication data rate Software settable default 125 Kbps Node address Software settable default 63 31713 M Front View Side View Top View Backplane Connector USB Port Front Panel D...

Страница 6: ...1756 DNB scanner 2 Select Tools and Node Commissioning 3 Browse to the DeviceNet network for the 1756 DNB scanner you want to commission 4 Select the 1756 DNB scanner you want to commission 5 In the Data Rate field select the communication data rate 6 Click Apply 7 Cycle power to the 1756 DNB scanner SettheNodeAddress The 1756 DNB scanner supports DeviceNet node addresses 00 63 The factory default...

Страница 7: ...ctory default communication rate and node address 1 Set the switches to 888 2 Restore power to the module When the out of box reset is complete the alphanumeric display repeatedly scrolls the message Reset Complete Change Switch Settings During this time the module does not respond to communication from any port including the backplane DeviceNet connector or USB port 3 After the module resets perf...

Страница 8: ...ector to the module DeviceNet port as shown Tighten the screws on the connector as needed IMPORTANT For detailed DeviceNet connection information see the DeviceNet Media Design and Installation Guide publication DNET UM072 Also see the Industrial Automation Wiring and Grounding Guidelines publication 1770 2 1 Color Chips dots Red Dot Black Dot Blue Dot White Dot 10 position Plug 5 position Plug 20...

Страница 9: ...Shock 0 C Ta 60 C 32 F Ta 140 F Temperature surrounding air max 60 C 140 F Voltage and current ratings Backplane 5 1V DC 400 mA DeviceNet Power 60 mA 11 2V DC CL 2 SELV limited to 100VA Isolation voltage 50V continuous Basic Insulation Type DeviceNet to Backplane No isolation between USB and Backplane Type tested at 860V AC for 60 s Terminal block torque specs DeviceNet connector 0 56 0 79 N m 5 7...

Страница 10: ...deos FAQs Chat User Forums and Product Notification Updates https rockwellautomation custhelp com Local Technical Support Phone Numbers Locate the phone number for your country http www rockwellautomation com global support get support now page Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer http www rockwellauto...

Отзывы: