ControlLogix DeviceNet Scanner Module

Set the Communication Rate

The 1756-DNB scanner supports the following DeviceNet network 
communication rates:

• 125  Kbps

• 250  Kbps

• 500  Kbps

The factory default setting is 125 Kbps.

Change the communication rate by setting the rotary switch or 
commissioning the 1756-DNB scanner in RSNetWorx™ for DeviceNet 
software. 

Use the switch to select a specific communication rate. When the 
switch is set to 3...9 (except for 888), you can configure the 
communication rate with RSNetWorx for DeviceNet software. When 
all three switches are set to 8, the 1756-DNB scanner resets to factory 
default settings at powerup.

See Restore the Factory Default Settings for more information.

See the following table for switch settings.

 

 Communication Rate Rotary Switch

Set the Rotary Switch

Use the communication (data) rate rotary switch to change the 
communication rate.

1. If the module is removed from the chassis, be sure that power is 

removed or the area is nonhazardous before proceeding.

2. Move the rotary switch to the desired position.

3. If necessary, reinstall the module into the chassis.

Use RSNetWorx for DeviceNet Software

Follow this procedure to use RSNetWorx for DeviceNet software to set 
the communication rate.

For more information, see the DeviceNet Modules in Logix5000™ 
Control Systems User Manual, publication 

 DNET-UM004

.

1. In RSNetWorx for DeviceNet software, select the 1756-DNB 

scanner.

2. Select Tools and Node Commissioning.

3. Browse to the DeviceNet network for the 1756-DNB scanner 

you want to commission.

4. Select the 1756-DNB scanner you want to commission.

5. In the Data Rate field, select the communication (data) rate.

6. Click Apply.

7. Cycle power to the 1756-DNB scanner.

Set the Node Address

The 1756-DNB scanner supports DeviceNet node addresses 00...63. 
The factory default setting is node address 63.

Change the node address by setting the rotary switches or 
commissioning the 1756-DNB scanner in RSNetWorx for DeviceNet 
software. 

Use the switches to select any network address from 00 through 63. 
When the switches are set outside of this range (except for 888), you 
can configure the node address with RSNetWorx for DeviceNet 
software. When all three switches are set to 8, the 1756-DNB scanner 
resets to factory default settings at powerup. See Restore the Factory 
Default Settings for more information. See the following table for 
switch settings. 

ATTENTION: 

Do not change the communication rate on an active 

network. Unpredictable operation may result. In addition, the new 
communication rate does not take effect until you cycle power to 
the 1756-DNB scanner.

Switch Settings and Communication Rate

Switch Setting

Communication Rate

0

125 Kbps

1

250 Kbps

2

500 Kbps

8

When all three switches are set to 8, this resets the 1756-DNB 
scanner to factory default settings.
Do not use for normal operation.

All other values

Select the communication rate with RSNetWorx for DeviceNet 
software.

Front of Module

Top of Module

Communication (Data) Rate Rotary Switch

IMPORTANT

For ease of access, remove the module from the chassis before 
proceeding.

Содержание ControlLogix DeviceNet

Страница 1: ...756 DNB 1756 DNBK ControlLogix DeviceNet scanners are devices that are used with various programmable controllers on the DeviceNet network Topic Page About the Module 5 Determine Module Slot Location 5 Change Module Settings 5 Install the Module in the Chassis 7 Specifications 9 Additional Resources 10 ...

Страница 2: ...code de pratique en vigueur Si cet équipement est utilisé d une façon qui n a pas été définie par le fabricant la protection fournie par l équipement peut être compromise 주의 본 제품 설치 설정 작동 또는 유지 보수하기 전에 본 문서를 포함하여 설치 설정 및 작동에 관한 참고 자료 섹션의 문서들을 반드시 읽고 숙지하 십시오 사용자는 모든 관련 규정 법규 및 표준에서 요구하는 사항에 대해 반드시 설치 및 배선 지침을 숙지해야 합니다 설치 조정 가동 사용 조립 분해 유지보수 등 모든 작업은 관련 규정에 따라 적절한 교육을 받은 사용자를 통해서만 수행해야 합니다 본 장비를 제조사...

Страница 3: ...itution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I Division 2 S assurer que l environnement est classé non dangereux avant de changer les piles European Hazardous Location Approval The following applies to products marked II 3 G Are Equipment Group II Equipment Category 3 and comply withthe Essential Health and Safety Requirements relating to t...

Страница 4: ...that can affect module operation Waste Electrical and Electronic Equipment WEEE Attheendofitslife thisequipmentshouldbecollectedseparatelyfromany unsorted municipal waste Prevent Electrostatic Discharge ATTENTION Thisequipmentissensitivetoelectrostaticdischarge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment Touch a grounded object...

Страница 5: ...ng in a 4 slot chassis Slot 0 is the first slot and is always the leftmost slot in the chassis ChangeModuleSettings The module ships with these settings Factory Setting Values Factory Settings Value Rotary switches 999 Communication data rate Software settable default 125 Kbps Node address Software settable default 63 31713 M Front View Side View Top View Backplane Connector USB Port Front Panel D...

Страница 6: ...1756 DNB scanner 2 Select Tools and Node Commissioning 3 Browse to the DeviceNet network for the 1756 DNB scanner you want to commission 4 Select the 1756 DNB scanner you want to commission 5 In the Data Rate field select the communication data rate 6 Click Apply 7 Cycle power to the 1756 DNB scanner SettheNodeAddress The 1756 DNB scanner supports DeviceNet node addresses 00 63 The factory default...

Страница 7: ...ctory default communication rate and node address 1 Set the switches to 888 2 Restore power to the module When the out of box reset is complete the alphanumeric display repeatedly scrolls the message Reset Complete Change Switch Settings During this time the module does not respond to communication from any port including the backplane DeviceNet connector or USB port 3 After the module resets perf...

Страница 8: ...ector to the module DeviceNet port as shown Tighten the screws on the connector as needed IMPORTANT For detailed DeviceNet connection information see the DeviceNet Media Design and Installation Guide publication DNET UM072 Also see the Industrial Automation Wiring and Grounding Guidelines publication 1770 2 1 Color Chips dots Red Dot Black Dot Blue Dot White Dot 10 position Plug 5 position Plug 20...

Страница 9: ...Shock 0 C Ta 60 C 32 F Ta 140 F Temperature surrounding air max 60 C 140 F Voltage and current ratings Backplane 5 1V DC 400 mA DeviceNet Power 60 mA 11 2V DC CL 2 SELV limited to 100VA Isolation voltage 50V continuous Basic Insulation Type DeviceNet to Backplane No isolation between USB and Backplane Type tested at 860V AC for 60 s Terminal block torque specs DeviceNet connector 0 56 0 79 N m 5 7...

Страница 10: ...deos FAQs Chat User Forums and Product Notification Updates https rockwellautomation custhelp com Local Technical Support Phone Numbers Locate the phone number for your country http www rockwellautomation com global support get support now page Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer http www rockwellauto...

Отзывы: