Monitor Connections
15-3
determine if communication has timed out
with a specific device
Enter the following rung for the device and add the specific action to occur:
If communication times out with a device (module) in the I/O configuration of the
controller, the controller produces a fault code for the module.
•
The GSV instruction gets the fault code for
module_name
and stores it in the
module_name_fault
tag.
•
If
module_name_fault
is not equal to 0, then the controller is not
communicating with the module.
interrupt the execution of logic and execute
the Controller Fault Handler
A. In the controller organizer, right-click the module and select
Properties
.
B. Click the
Connection
tab.
C. Select (check) the
Major Fault If Connection Fails While in Run Mode
check box.
D. Develop a routine for the Controller Fault Handler. See the
Logix5000 Controllers
Common Procedures
, publication 1756-PM001.
If you want to:
Then:
Get System Value
CIP Object Class
MODULE
CIP Object Name module_name
Attribute Name
FaultCode
Dest
module_name_fault
GSV
Not Equal
Source A module_name_fault
Source B
0
NEQ
42468
Where:
Is a:
module_name
name of the module from the I/O configuration
module_name_fault
DINT tag that stores the fault code for the module
Содержание controllogix 1756-L63
Страница 1: ...ControlLogix System 1756 L1 L1Mx L55Mxx L63 User Manual Allen Bradley HMIs...
Страница 4: ...Publication 1756 UM001E EN P August 2002 Summary of Changes 2 Notes...
Страница 16: ...Publication 1756 UM001E EN P August 2002 Table of Contents x...
Страница 46: ...Publication 1756 UM001E EN P August 2002 2 4 Download and Go Online over an EtherNet IP Network Notes...
Страница 116: ...Publication 1756 UM001E EN P August 2002 6 16 Communicate with a PanelView Terminal Over a EtherNet IP Network Notes...
Страница 156: ...Publication 1756 UM001E EN P August 2002 8 16 Communicate with 1756 I O over a ControlNet Network Notes...
Страница 184: ...Publication 1756 UM001E EN P August 2002 9 28 Communicate with 1771 I O Over a ControlNet Network Notes...
Страница 200: ...Publication 1756 UM001E EN P August 2002 10 16 Communicate with 1794 I O Over a ControlNet Network Notes...
Страница 218: ...Publication 1756 UM001E EN P August 2002 11 18 Communicate with Another Controller over a ControlNet Network Notes...
Страница 222: ...Publication 1756 UM001E EN P August 2002 12 4 Route PLC 5 Messages Between ControlNet Networks Notes...
Страница 268: ...Publication 1756 UM001E EN P August 2002 15 4 Monitor Connections Notes...
Страница 276: ...Publication 1756 UM001E EN P August 2002 16 8 Communicate with a DeviceNet Device Notes...
Страница 306: ...Publication 1756 UM001E EN P August 2002 18 8 Route PLC 5 or SLC 500 Messages From a DH Network Notes...
Страница 368: ...Publication 1756 UM001E EN P August 2002 22 18 Configure DF1 Master and Slave Communications Notes...
Страница 402: ...Publication 1756 UM001E EN P August 2002 24 22 Program Motion Control Notes...
Страница 408: ...Publication 1756 UM001E EN P August 2002 25 6 Maintain the 1756 BA1 Battery Notes...
Страница 418: ...Publication 1756 UM001E EN P August 2002 B 2 Estimate Execution Time...
Страница 420: ...Publication 1756 UM001E EN P August 2002 C 2 Estimate Memory Use...
Страница 422: ...Publication 1756 UM001E EN P August 2002 D 2 Determine When Data Is Updated Notes...
Страница 424: ...Publication 1756 UM001E EN P August 2002 E 2 Reconfigure an I O module Notes...
Страница 428: ...Publication 1756 UM001E EN P August 2002 4 Index...
Страница 429: ...Publication 1756 UM001E EN P August 2002 Index 5 Allen Bradley HMIs...
Страница 430: ...Publication 1756 UM001E EN P August 2002 6 Index...
Страница 435: ...ControlLogix System User Manual Allen Bradley HMIs...