1
Publication 1756-UM532A-EN-P - May 2006
Appendix
A
Specifications
ControlLogix DH-485 Communications Module 1756-DH485
Attribute
Value
Module Location
ControlLogix chassis
Maximum Backplane
Current Load
850 mA @ +5.1V dc and 1.7mA @ 24V dc
from I/O chassis backplane
Power Dissipation
4.5 W
Thermal Dissipation, Max
15.4 BTU/hr
Isolation Voltage
50V
Tested to withstand 750V dc for 60 s
Available Communication Rates
19.2 Kbps (default) and 9600 Kbps
Wiring Category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, Industrial
Automation Wiring and Grounding Guidelines.
2 - on communications ports
Environmental Specifications
Attribute
Value
Operational Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60 °C (32...140 °F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40...85 °C (-40...185 °F)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5...95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500 Hz
Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Non-operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
CISPR 11:
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80%AM from 80...2000 MHz
10 V/m with 200 Hz 50% Pulse 100% AM at 900 Mhz
Содержание ControlLogix 1756-DH485
Страница 1: ...ControlLogix DH 485 Communication Module 1756 DH485 User Manual...
Страница 8: ...Publication 1756 UM532A EN P May 2006 Preface ii Notes...
Страница 18: ...Publication 1756 UM532A EN P May 2006 1 10 1756 DH485 Module Overview Notes...
Страница 32: ...Publication 1756 UM532A EN P May 2006 2 14 Overview of the DH 485 Network Notes...
Страница 72: ...Publication 1756 UM532A EN P May 2006 6 12 Communicate Between SLC Controllers over DH and DH485 Networks Notes...
Страница 102: ...Publication 1756 UM532A EN P May 2006 B 6 Troubleshoot the 1756 DH485 Module Notes...
Страница 106: ...Publication 1756 UM532A EN P May 2006 iv Index Notes...
Страница 109: ......