Publication 1756-UM532A-EN-P - May 2006
3-6
Use Data Highway 485 Network
This figure shows an example of remote DH-485 messaging between SLC/03
(or later) controller A and SLC 5/03 (or later) controller B. In this example, the
following information must be included in the remote DH-485 message
routing message instruction:
•
Local DH-485 node = 020
•
Destination link ID = 2
•
Remote DH-485 node = 030
Remote DH-485 Messaging Between
SLC 5/03 Controller A and SLC 5/03 Controller B
Link IDs
To use remote DH-485 messaging, each network that is an originating network
or target network must have a unique link ID. The 1756-DH485 module
requires these link IDs to be decimal values between 1-199. Each DH-485
channel on a 1756-DH485 module must have its own unique link ID.
TE
RM
T T
A A A A
B B
ControlLogix Chassis
SLC 5/03 Controller A
Link ID 1
SLC 5/03 Controller B
Link ID 2
Channel A - Node: 020
Channel B - Node: 025
1756-DH485 Module
44053
AIC+
AIC
AIC+
AIC
Node: 030
Содержание ControlLogix 1756-DH485
Страница 1: ...ControlLogix DH 485 Communication Module 1756 DH485 User Manual...
Страница 8: ...Publication 1756 UM532A EN P May 2006 Preface ii Notes...
Страница 18: ...Publication 1756 UM532A EN P May 2006 1 10 1756 DH485 Module Overview Notes...
Страница 32: ...Publication 1756 UM532A EN P May 2006 2 14 Overview of the DH 485 Network Notes...
Страница 72: ...Publication 1756 UM532A EN P May 2006 6 12 Communicate Between SLC Controllers over DH and DH485 Networks Notes...
Страница 102: ...Publication 1756 UM532A EN P May 2006 B 6 Troubleshoot the 1756 DH485 Module Notes...
Страница 106: ...Publication 1756 UM532A EN P May 2006 iv Index Notes...
Страница 109: ......