Publication 1756-UM532A-EN-P - May 2006
Communicate Between SLC Controllers over DH+ and DH485 Networks
6-9
Create the Routing Table in RSLinx Software
These are the routing tables needed for the example configuration.
In this example, the:
•
SLC 5/03 controller is connected
to Channel A of the 1756-DH485
module. The 1756-DH485 node
address on the DH-485 network
is node 0.
•
1756-DHRIO and the
1756-DH485 modules are on the
same backplane.
•
1756-DH485 module is in slot 14.
•
1756-DHRIO module is in slot 8.
•
Link ID of Channel B of the
1756-DHRIO is Link 20.
•
SLC 5/04 controller is connected
to Channel B of the
1756-DHRIO.
•
node address of the SLC 5/04
controller on DH+ is 10 octal or
8 decimal.
•
SLC 5/03 controller initiates a
remote message to the SLC 5/04
controller.