Thermocouple Descriptions
Type J thermocouples are recommended by the ASTM [5] for use in the
temperature range from 0°C to 760°C in vacuum, oxidizing, reducing, or
inert atmospheres. If used for extended times in air above 500°C, heavy
gauge wires are recommended because the oxidation rate is rapid at
elevated temperatures. Oxidation normally causes a gradual decrease in
the thermoelectric voltage of the thermocouple with time. Because iron
rusts in moist atmospheres and may become brittle, type J thermocouples
are not recommended for use below 0°C. In addition, they should not be
used unprotected in sulfurous atmospheres above 500°C.
The positive thermoelement, iron, is relatively insensitive to composition
changes under thermal neutron irradiation, but does exhibit a slight
increase in manganese content. The negative thermoelement, a
copper-nickel alloy, is subject to substantial composition changes under
thermal neutron irradiation since copper is converted to nickel and zinc.
Iron undergoes a magnetic transformation near 769°C and an
alpha-gamma crystal transformation near 910°C [6]. Both of these
transformations, especially the latter, seriously affect the thermoelectric
properties of iron, and therefore of type J thermocouples. This behavior
and the rapid oxidation rate of iron are the main reasons why iron versus
constantan thermocouples are not recommended as a standardized type
above 760°C. If type J thermocouples are taken to high temperatures,
especially above 900°C, they will lose the accuracy of their calibration
when they are recycled to lower temperatures. If type J thermocouples
are used in air at temperatures above 760°C, only the largest wire, AWG 8
(3.3 mm) should be used and they should be held at the measured
temperature for 10 to 20 minutes before readings are taken. The
thermoelectric voltage of the type J thermocouples may change by as
much as 40
µ
V (or 0.6°C equivalent) per minute when first brought up to
temperatures near 900°C.
ASTM Standard E230-87 in the 1992 Annual Book of ASTM Standards [7]
specifies that the initial calibration tolerances for type J commercial
thermocouples be ±2.2°C or ±0.75 percent (whichever is greater) between
0°C and 750°C. Type J thermocouples can also be supplied to meet
special tolerances, which are equal to approximately one-half the
standard tolerances given above. Tolerances are not specified for type J
thermocouples below 0°C or above 750°C.
The suggested upper temperature limit of 760°C given in the above ASTM
standard [7] for protected type J thermocouples applies to AWG 8 (3.25
mm) wire. For smaller diameter wires the suggested upper temperature
limit decreases to 590°C for AWG 14 (1.63 mm), 480°C for AWG 20 (0.81
mm), 370°C for AWG 24 or 28 (0.51 mm or 0.33 mm), and 320°C for AWG
30 (0.25 mm). These temperature limits apply to thermocouples used in
conventional closed-end protecting tubes and they are intended only as a
rough guide to the user. They do not apply to sheathed thermocouples
having compacted mineral oxide insulation.
Содержание CompactBlock LDX 1790D-4T0
Страница 1: ...CompactBlock LDX I O Thermocouple Modules 1790D T4T0 1790D 4T0 1790P T4T0 User Manual AB Drives ...
Страница 2: ......
Страница 8: ...Publication 1790 UM003A EN P May 2002 viii ...
Страница 50: ...Publication 1790 UM003A EN P 3 20 Module Data Status and Channel Configuration for DeviceNet ...
Страница 56: ...Publication 1790 UM003A EN P 4 6 Diagnostics and Troubleshooting ...
Страница 102: ...Publication 1790 UM003A EN P G 4 ...
Страница 108: ...Publication 1790 UM003A EN P May 2002 I 6 ...
Страница 111: ...AB Drives ...