Publication 1790-UM003A-EN-P
Overview
1-5
Module Operation - DeviceNet Example
When the module recieves a differential input from an analog device, the
module’s circuitry multiplexes the input into an A/D converter. The
converter reads the signal and converts it as required for the type of input.
The module also continuously samples the CJC sensors and compensates
for temperature changes at the terminal block cold junction, between the
thermocouple wire and the input channel. See the block diagram below.
Figure 1.3 Block Diagram
Each channel can receive input signals from a thermocouple or millivolt
analog input device, depending upon how you configured the channel.
When configured for thermocouple input types, the module converts the
analog input voltages into cold-junction compensated and linearized
digital temperature readings. The module uses the National Institute of
Standards and Technology (NIST) ITS-90 standard for linearization for all
thermocouple types (J, K, T, E, R, S, B, N).
When configured for millivolt inputs, the module converts the analog
values directly into digital counts.
Input
CH0
Multiplexer
VA2
A/D
VREF
Vref
Channel Select
Channels 1 through 3 same as
channel 0 above.
43309
A
B
VA1
Vcc
Optical
Isolation
AIN-
AIN+1
VA3
A-GND
Micro-
Controller
Transmit
Receive
GND
Network
Power
Supply
Analog
Power
Supply
DeviceNet
24Vdc
Power
Vcc
GND
VA1
VA2
VA3
A-GND
VDC
GND
1
2
3
Auxiliary
24Vdc
Power
Transceiver
+
_
Содержание CompactBlock LDX 1790D-4T0
Страница 1: ...CompactBlock LDX I O Thermocouple Modules 1790D T4T0 1790D 4T0 1790P T4T0 User Manual AB Drives ...
Страница 2: ......
Страница 8: ...Publication 1790 UM003A EN P May 2002 viii ...
Страница 50: ...Publication 1790 UM003A EN P 3 20 Module Data Status and Channel Configuration for DeviceNet ...
Страница 56: ...Publication 1790 UM003A EN P 4 6 Diagnostics and Troubleshooting ...
Страница 102: ...Publication 1790 UM003A EN P G 4 ...
Страница 108: ...Publication 1790 UM003A EN P May 2002 I 6 ...
Страница 111: ...AB Drives ...