Faults & Troubleshooting
Other Displays
The motor does not accelerate properly.
1. Check to see that a frequency has been commanded.
2. Check to see if a preset frequency has been selected.
3. Check to see if the motor load is too high.
4. Check to see if the acceleration time is too long.
5. Check to see if manual boost and current limit are set properly.
The speed of the motor does not match the
frequency.
1. Check to see that the maximum frequency has been entered
correctly.
2. Check the rated speed of the motor and the reduction ratio of
the gear.
3. Check to see if manual boost and current limit are set properly.
4. If PID control is used, check gain adjustments.
The motor runs unstable.
1. If sudden high load changes occur, choose a drive and motor
with higher ratings or reduce the load changes.
2. If resonant frequencies occur in the motor, set up skip
frequency bands.
3. If the input voltage is not constant, change the PWM carrier
frequency.
The parameters stored do not match the values
entered.
1. When the input voltage was switched off the entered values
were transferred to the power-failure safe EEPROM.
Reprogram the values and wait at least 6 seconds before
powering down.
No entries can be made.
1. Check to see if the parameter protection is activated via a
digital input setting of 15 {SFT}.
The electronic motor protection (fault E05) is
triggered.
1. Check the manual boost setting to see if it is too high.
2. Check the electronic motor protection setting to make sure that
it is correct.
Display
Description
A reset signal has been issued.
The Bulletin 161 drive is in standby mode.
Note: If motor was running when the 18 {RS} input was received, the motor will coast to a
stop.
The input voltage has been switched off.
The waiting time before automatic restart has expired (see
P
b01
-[Restart Mode Select]
-
P
b03
-
[Restart time]
).
The factory setting has been selected and the drive is in the initialization phase
(see
P
b84
-[Reset Functions],
P
b85
-[Factory Defaults Select]
). If your drive is a K version,
parameters for the 50Hz version are loaded. If your drive is a U version, parameters for the 60 Hz
version are loaded.
No data present or the function is not active.
Problem
Corrective Action
- - -