     ArmorPoint DeviceNet Adapters, Series A

Specifications

Following are specifications for the 1738 ArmorPoint DeviceNet 
adapters.

ArmorPoint DeviceNet Adapters - 1738-ADN12, -ADN18, -ADN18P, and -ADNX

Expansion I/O Capacity

DeviceNet adapter backplane current output = 1.0A maximum. 
See the list below for backplane current consumption for each 
ArmorPoint I/O catalog number and the current consumption 
for each of the ArmorPoint modules connected to the 
ArmorPoint DeviceNet adapter. Verify that it is below 1.0A.

Backplane current can be extended beyond 1.0A with a 
1738-EP24DC Backplane Extension Power Supply. The 
1738-EP24DC can supply up to an additional 1.3A of backplane 
current.

Multiple 1738-EP24DC modules can be used to reach the 
maximum of 63 modules. 

 

 

Cat. No.

PointBus Current Requirements

 

1738-IB2M12 75mA

 

1738-IB4xxx  75mA

 

1738-IB8xxx 75mA

 

1738-IV4xxx 75mA

 

1738-OB2EM12

75mA

 

1738-OB2EPM12

75mA

 

1738-OB4Exxx

75mA

 

1738-OB8Exxx

75mA

 

1738-OV4EM12

75mA

 

1738-OW4xxx 90mA

 

1738-IE2CM12 75mA

 

1738-OE2CM12

75mA

 

1738-IE2VM12 75mA

 

1738-OE2VM12 75mA

 

1738-IA2xxx 75mA

 

1738-OA2xxx 75mA

 

1738-IJM23

160mA

 

1738-SSIM23

110mA

 

1738-IR2M12 220mA

 

1738-IT2IM12 175mA

 

1738-VHSC24M23 180mA

 

1738-232ASCM12

75mA

 

1738-485ASCM12

75mA

DeviceNet Communication Rate

125K bit/s (500m maximum)

 

250K bit/s (250m maximum)

 

500K bit/s (100m maximum)

DeviceNet Cable

Allen-Bradley part number 1485C-P1-Cxxx

 

Refer to publication DN-2.5 for more information

Содержание ArmorPoint DeviceNet 1738-ADN12

Страница 1: ...The DeviceNet adapters are shown below DeviceNet X10 X1 Adapter Status DeviceNet Status PointBus Status System Power Adapter Power 1738 ADN18 PWR 1738 ADN18P DNet In DNet Out X1 Adapter Status Device...

Страница 2: ...with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automat...

Страница 3: ...t should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication Subsequent sections of this...

Страница 4: ...g screws ATTENTION Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when yo...

Страница 5: ...Manager or another software configuration tool Setting the switches at any number from 64 through 99 lets the software have address control Each module is shipped with the switches set for node addres...

Страница 6: ...cur which is indicated by a flashing red Adapter Status LED Settings of 64 through 99 cause the module to use the last valid node address stored internally Example The last setting internally was 40 I...

Страница 7: ...nnections against leaks and maintain IP67 requirements view into connector Pin 1 Drain Pin 2 V Pin 3 V Pin 4 CAN_High Pin 5 CAN_Low 43764 Male In Connector Female Out Connector 1738 ADN12 Subnet out 1...

Страница 8: ...y Flashing Red Recoverable fault Red Unrecoverable fault may require device replacement Flashing Red Green Device is in self test DeviceNet Status Off Device is not on line Device attempting to AutoBa...

Страница 9: ...evice the device has detected a network access error and is in communication faulted state Device has received and accepted an Identify Communication Faulted Request long protocol message PointBus Sta...

Страница 10: ...on Power Supply The 1738 EP24DC can supply up to an additional 1 3A of backplane current Multiple 1738 EP24DC modules can be used to reach the maximum of 63 modules Cat No PointBus Current Requirement...

Страница 11: ...er single fault conditions A PELV supply has the same rating and is connected to protected earth Input Voltage Rating 24V dc 10 28 8V dc range Input Overvoltage Protection Reverse polarity protected I...

Страница 12: ...on shielded ports Conducted RF Immunity IEC 61000 4 6 10Vrms with 1kHz sine wave 80 AM from 150kHz to 80MHz Emissions CSPR 11 Group 1 Class A Enclosure Type Rating Meets IP65 66 67 when marked Mountin...

Страница 13: ...Publication 1738 IN014A EN E June 2004 ArmorPoint DeviceNet Adapters Series A 13 Notes Allen Bradley Drives...

Страница 14: ...e module within the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your...

Отзывы: