5
3.
Mount the adapter and I/O bases using #8 (M4) screws.
4.
Ground the system using the ground lug connection in the I/O
base. (The ground lug connection is also a mounting hole.)
5.
Mount the terminating base that was shipped with the adapter as
the last base in the backplane instead of the base that was
shipped with the I/O module.
Set the Node Address
Valid node addresses are
00
through
63
.
Set the node address using either the rotary switches, RSNetWorx for
DeviceNet
, DeviceNetManager
, or another software configuration
tool. Setting the switches at any number from
64
through
99
lets the
software have address control.
Each module is shipped with the switches set for node address
63
.
Remove the caps on the front of the module to access the switches
(refer to the illustrations on page 1). The two switches are:
•
X10 (most significant digit) - left side of module
•
X1 (least significant digit) - right side of module
To reset the node address, use a small blade screwdriver to rotate the
switches. Line up the small notch on the switch with the number
setting you wish to use and then cycle power.
Terminating base
43787
Mounting hole
Latching mechanism
Ground connection
31433-M
This example shows the
node address set at 63.
Allen-Bradley Drives