Rockwell Automation Publication GMSP-IN002A-EN-P - March 2016

3

Remote Monitoring for PowerFlex 755 AC Drive

Remote Monitoring Kit

Included with your service contract is a hardware kit used to connect your PowerFlex™ 755 Drive to the Rockwell Automation™ remote monitoring 
platform. 

Gateway Device

The gateway device is the bridge between your PowerFlex 755 drive and the Rockwell Automation remote monitoring platform. The version 
ordered determines the gateway device. Catalog number 9300-VSELV uses an Ethernet connection to access the Internet, for which the Netbiter 
EC310 is provided. Catalog number 9300-VSELVCELL uses a cellular data connection to access the Internet, for which the Netbiter EC350 is 
provided. The Netbiter EC350 is delivered preloaded with an AT&T SIM card. 

DIN Rail Mounting Kit

The DIN rail mounting kit provided is compatible with both the Netbiter EC310 and Netbiter EC350.

1 and 3 meter Ethernet Cables

To assist with the network connections described in this manual, two Ethernet cables with RJ45 connectors are provided.

Antenna with 4 meter cable (Cat. No. 9300-VSELVCELL)

With the cellular version, a screw mount antenna with an extended 4 meter cable is provided to connect to the Netbiter EC350 as discussed in this 
manual.

Field Mounting Instructions

Use the following information to install the included hardware to enable the Remote Monitoring service.

Gateway Mounting

The Netbiter gateway hardware is a DIN rail (Type EN50022) mounted device with dimensions (H x W x D) of 1.01 x 5.31 x 3.62 in. 
(25.6 x 135 x 92 mm). The mounting space on the DIN rail must be large enough to accommodate the size of the gateway plus an additional 1 inch 
(25.4 mm) clearance space from other components on the DIN rail. 

Cellular Antenna Mounting

The Netbiter EC350, the cellular version of the gateway device, must use the provided antenna to establish a live connection to the Rockwell 
Automation remote monitoring platform. Additional steps need to be taken to install the screw mount antenna that is included with the VSE kit. 
The antenna itself must not be mounted within an enclosure to avoid inhibiting signal strength. The 13.1 ft. (4 m) antenna cable connects to the 
Netbiter, using the screw connection as shown in the Network Connection Instructions section below.

If the Netbiter is mounted within an enclosure, a 0.63 in. (16 mm) hole must be drilled such that the antenna cord can be routed through the hole 
and connected to the Netbiter without causing any obstruction.

IMPORTANT

Do not mount antenna inside a metal enclosure. An enclosure reduces the strength of cell signal. A 13.1 ft. (4 m) extension cable is included to help mount 
the antenna outside the enclosure.

Содержание 9300-VSELV

Страница 1: ...Instructions Remote Monitoring for PowerFlex 755 AC Drive Catalog Numbers 9300 VSELV and9300 VSELVCELL Topic Page Remote Monitoring Kit 3 Field Mounting Instructions 3 Connection Instructions 4 Apply Power 6 Verify Internet Connection 6 ...

Страница 2: ... code de pratique en vigueur Si cet équipement est utilisé d une façon qui n a pas été définie par le fabricant la protection fournie par l équipement peut être compromise 주의 본 제품 설치 설정 작동 또는 유지 보수하기 전에 본 문서를 포함하여 설치 설정 및 작동에 관한 참고 자료 섹션의 문서들을 반드시 읽고 숙지하 십시오 사용자는 모든 관련 규정 법규 및 표준에서 요구하는 사항에 대해 반드시 설치 및 배선 지침을 숙지해야 합니다 설치 조정 가동 사용 조립 분해 유지보수 등 모든 작업은 관련 규정에 따라 적절한 교육을 받은 사용자를 통해서만 수행해야 합니다 본 장비를 제조...

Страница 3: ...manual FieldMountingInstructions Use the following information to install the included hardware to enable the Remote Monitoring service GatewayMounting The Netbiter gateway hardware is a DIN rail Type EN50022 mounted device with dimensions H x W x D of 1 01 x 5 31 x 3 62 in 25 6 x 135 x 92 mm The mounting space on the DIN rail must be large enough to accommodate the size of the gateway plus an add...

Страница 4: ...lling a Netbiter EC310 the Ethernet WAN port connects to the enterprise Internet network Your Internet firewall is required to allow a Port 443 outbound connection to https www ramonitoring com and xx netbiter net the xx indicating the complete range Access to a domain name system DNS server is also required The WAN port is not used for the Netbiter EC350 If installing the Netbiter EC350 connect t...

Страница 5: ...ssibleLANTopologies IMPORTANT WheninstallingaNetbiter EC310 theEthernet WANport connects to your internet network Yourinternet firewallis requiredtoallow aPort 443outbound connection to https www ramonitoring com and xx netbiter net the xx indicating the complete range Access to a domain name system DNS server is also required ...

Страница 6: ...e Monitoring for PowerFlex 755 AC Drive ApplyPower The Netbiter EC310 EC350 devices require a 12 48V DC power source to be powered on Connect the Netbiter to the power source as described in the schematic below EC310 EC350PowerandGroundWiring VerifyInternetConnection ...

Страница 7: ...ting up Steady green Normal operation Updating green Firmware update in progress Steady red Hardware failure contact support Updating red Application failure contact support Power OFF No power Steady green Unit has power Ethernet Link located on RJ45 ports OFF No network detected Orange flicker Activity on 10 Mbps Ethernet network Green flicker Activity on 100 Mbps Ethernet network Specifications ...

Страница 8: ...y suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center Knowledgebase Articles How to Videos FAQs Chat User Forums and Product Notification Updates https rockwellautomation custhelp com Local Technical Support Phone Numbers Locate the phone number for yo...

Отзывы: