Precautions
Read and follow these precautions for use.
Environment and Enclosure Information
European Union Directive Compliance
This product meets the European Union Directive requirements when installed within the European
Union or EEA regions and have the CE mark. A copy of the declaration of the conformity is
available at
http://www.rockwellautomation.com/rockwellautomation/certification/overview.page
.
ATTENTION:
This equipment is intended for use in a Pollution Degree 2 industrial environment, in
overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to
2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR
Publication 11. Without appropriate precautions, there may be potential difficulties ensuring
electromagnetic compatibility in other environments due to conducted as well as radiated
disturbance.
This equipment is supplied as open type equipment. UL recognized equipment must be mounted
within an enclosure that is suitably designed for those specific environmental conditions that are
present and appropriately designed to prevent personal injury resulting from accessibility to live
parts. The interior of the enclosure must be accessible only by the use of a tool. UL listed
equipment need not be mounted inside another enclosure. Subsequent sections of this publication
may contain additional information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see the following:
•
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
, for additional
installation requirements
•
NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of
the degrees of protection provided by different types of enclosure
ATTENTION:
This equipment is intended to operate in an industrial or control room environment,
which uses some form of power isolation from the public low-voltage mains. Some computer
configurations may not comply with the EN 61000-3-2 Harmonic Emissions standard as specified
by the EMC Directive of the European Union. Obtain permission from the local power authority
before connecting any computer configuration that draws more than 75 W of AC power directly
from the public mains.
To comply with EN 55024 and EN 61000-6-2, the Ethernet port LAN cable must be less than 30 m
(98.42 ft), used only indoors, and not exit the building at any point. All other I/O cables must be
less than 3 m (9.84 ft) and used only indoors.