Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Chapter 6
Configure a Standard Module
Counters Category
The Counters category is available only if you choose a value for Counters in
the Module Definition dialog box.
The Counters category shows the configuration options available for each
counter. Based on your Input Filter Time selections, the Input Filter Time
Off→On and On→Off times change. You can also configure the counter Preset
value and enable Rollover at Preset.
IMPORTANT
The total number of Counters subtracts from the available number of Points.
For example, if you configure a 5069-IB16F module to use four counters, the
first four terminals are not available to use as points.
The number of points available on the module in this case is 12. That is,
points 4…15.
The maximum number of counters that can be configured is eight channels.
That is, counters 0…7.
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......