Rockwell Automation Publication 193-UM014C-EN-P - August 2016
55
Automatic Device Recovery or Replace
Chapter 6
5. Click Save, then cycle power on the EtherNet/IP communication
auxiliary module.
An ADR download is performed immediately before the DeviceNet
master allocates an I/O connection. For an ADR download to occur, the
PLC must be online and scanning. See
online with the controller.
If the download is unsuccessful, an “ADR Error” for the appropriate
node is reported in the corresponding “Scan List Entry Status Word”. If
the electronic keys for the device at a given node address do not match
the saved electronic keys, no ADR download takes place, an I/O
connection is not allocated, and a “Keying Mismatch” is reported in the
corresponding “Scan List Entry Status Word”.
After you enable the ADR, a warning appears if you change the scan list.
The EtherNet/IP communication auxiliary module also supports Auto
Address Recovery (AAR). When the EtherNet/IP communication auxiliary
module detects that a node is missing from the scan list and a module matching
Содержание 193-DNENCAT
Страница 6: ...6 Rockwell Automation Publication 193 UM014C EN P August 2016 Table of Contents Notes...
Страница 8: ...8 Rockwell Automation Publication 193 UM014C EN P August 2016 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 193 UM014C EN P August 2016 Preface Notes...
Страница 18: ...18 Rockwell Automation Publication 193 UM014C EN P August 2016 Chapter 1 Installation and Wiring Notes...
Страница 38: ...38 Rockwell Automation Publication 193 UM014C EN P August 2016 Chapter 3 Configure the DeviceNet Network Notes...
Страница 80: ...80 Rockwell Automation Publication 193 UM014C EN P August 2016 Chapter 8 Email Text Notes...
Страница 90: ...90 Rockwell Automation Publication 193 UM014C EN P August 2016 Chapter 10 Troubleshooting Notes...
Страница 108: ...108 Rockwell Automation Publication 193 UM014C EN P August 2016 Appendix B EtherNet IP and DeviceNet Information Notes...
Страница 111: ......