Publication 1794-6.5.12 - November 1997
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
4
-9
Chapter Summary
In this chapter, you learned how to configure your module’s features and
enter your data.
word 1 cont.
Bits 14-15
(16-17)
Input Type Select
Bit
15
14
Input type selection for channels 4-7
0
0
Thermocouple
0
1
RTD
1
0
Not used
1
1
Write Word 2
00-15 (00-17)
RTD loop resistance offset select bits
– used when input type is set to RTD and
sensor mode select is set to 2-wire with loop resistance compensation. Allows you to
set the type of RTD loop resistance compensation used for all RTDs or one of three fixed
values for all channels.
NOTE:
Not applicable to 10
Ω
copper RTD, which defaults to 0
Ω
.
Bit
01
00
RTD channel 0
Bit
03
02
RTD channel 1
Bit
05
04
RTD channel 2
Bit
07
06
RTD channel 3
Bit
09
08
RTD channel 4
Bit
11
10
RTD channel 5
Bit
13
12
RTD channel 6
Bit
15
14
RTD channel 7
0
0
Use channel loop compensation value stored during calibration
procedure for 2-wire RTD (default = 0
Ω
)
0
1
5
Ω
1
0
10
Ω
1
1
15
Ω
Write Word 3
00-07
Extended data table command data bits –
These bits are written to the module
during calibration. They are used to define offset, gain and general channel calibration.
08-14 (10-16)
Extended data table command bits –
These bits are written to the module during
calibration. They are used to select channel calibration action.
15 (17)
Reserved for factory use only
Word
Dec. Bits
(Octal Bits)
Description
Содержание 1794-IRT8
Страница 1: ...User Manual Thermocouple RTD Millivolt Input Module Cat No 1794 IRT8 Allen Bradley Allen Bradley PLCs ...
Страница 3: ...Publication 1794 6 5 12 November 1997 2 Allen Bradley PLCs ...
Страница 7: ...Publication 1794 6 5 12 November 1997 P 4 Using This Manual Allen Bradley PLCs ...
Страница 33: ...Publication 1794 6 5 12 November 1997 3 6 Programming Your Thermocouple RTD Input Module Allen Bradley PLCs ...