Publication 1794-6.5.12 - November 1997
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
4
-3
Reading Data From Your
Module
Read programming moves status and data from the TC/RTD input module
to the processor’s data table in one I/O scan. The processor’s user
program initiates the request to transfer data from the TC/RTD input
module to the processor.
Mapping Data for the
Thermocouple/RTD/mV
Module
The following read and write words and bit/word descriptions describe
the information written to and read from the TC/RTD input module. The
module uses up to 11 words of input data and up to 4 words of output
data. Each word is composed of 16 bits.
Thermocouple/RTD Input Module (1794-IRT8) Image Table
Mapping
Thermocouple/RTD/mV Input Module (1794-IRT8) Read Words
Module Image
I/O Image
Input Data Channel 0
Input Data Channel 1
Input Data Channel 2
Input Data Channel 3
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 7
Underrange
Input Size
Output Size
0 to 4 Words
1 to 11 Words
Overrange
Diagnostics
CJC
Alarms
EDT command and response
RFlg
EDT command and data
CFlg
RTD Offsets for each channel
Sensor Type
Sensor Type
Mode
Mode
TC/RTD
TC/RTD
Filter Cut
Reference Jct
Data Format
FM
Decimal
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Octal
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Word
⇓
Read
0
Channel 0 Input Data
1
Channel 1 Input Data
2
Channel 2 Input Data
3
Channel 3 Input Data
4
Channel 4 Input Data
5
Channel 5 Input Data
6
Channel 6 Input Data
7
Channel 7 Input Data
Содержание 1794-IRT8
Страница 1: ...User Manual Thermocouple RTD Millivolt Input Module Cat No 1794 IRT8 Allen Bradley Allen Bradley PLCs ...
Страница 3: ...Publication 1794 6 5 12 November 1997 2 Allen Bradley PLCs ...
Страница 7: ...Publication 1794 6 5 12 November 1997 P 4 Using This Manual Allen Bradley PLCs ...
Страница 33: ...Publication 1794 6 5 12 November 1997 3 6 Programming Your Thermocouple RTD Input Module Allen Bradley PLCs ...