Appendix
B
Publication 17946.5.2 - May 1996
Differences Between Series A
and Series B Analog Modules
The following lists major differences between series A and series B
analog modules.
Catalog Number
Description
Series A
Series B
1794IE8,
1794OE4,
1794IE4XOE2
Power Up bit in Read Word
None
This bit is set when all bits in the
configuration register are 0 (unconfigured
state).
Change to range selection
tables
No off position available. Module
produces either 2V or 4mA, dependent
upon the range selected, until module is
configured.
Off position now produces 0V or 0mA,
dependent upon range selected, until
module is configured.
Specifications
1794OE4
Output Current Terminal
4mA output until module is configured
420mA user configurable
020mA user configurable
0mA output until module is configured
420mA user configurable
020mA user configurable
Output Voltage Terminal
2V output until module is configured
±
10V user configurable
0-10V user configurable
0V output until module is configured
±
10V user configurable
0-10V user configurable
1794IE4XOE2
Output Current Terminal
4mA output until module is configured
420mA user configurable
020mA user configurable
0mA output until module is configured
420mA user configurable
020mA user configurable
Output Voltage Terminal
2V output until module is configured
±
10V user configurable
0-10V user configurable
0V output until module is configured
±
10V user configurable
0-10V user configurable
1794IE8,
1794OE4,
1794IE4XOE2
Agency Certification
(when product or packaging is
marked)
•
CSA certified
•
CSA Class I, Division 2, Groups A, B,
C, D certified
•
UL listed
•
CSA certified
•
CSA Class I, Division 2, Groups A, B,
C, D certified
•
UL listed
•
CE marked for all applicable directives