4–5
Configuring Your Module and Reading Status from Your Module with a Remote I/O Adapter
Publication 17946.5.2 - May 1996
Range Selection Bits for the 1794-IE8/B Analog Input Module
Channel No.
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
F0
C0
F1
C1
F2
C2
F3
C3
F4
C4
F5
C5
F6
C6
F7
C7
Decimal Bits
(Octal Bits)
00
08
(10)
01
09
(11)
02
10
(12)
03
11
(13)
04
12
(14)
05
13
(15)
06
14
(16)
07
15
(17)
0-10V dc/0-20mA
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
4-20mA
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
10 to +10V dc
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Off
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
C = Configure select bit
F = Full range bit
1 When configured to off, individual channels will return 0000H on Series B modules, and 4 to 20mA on Series A modules.
Word/Bit Descriptions for the 1794-IE8/B Analog Input Module
Write
Word
Decimal Bit (Octal Bit)
Definition
Write
Bits 00-07
Full range bits (F)
for individual channels - Bit 00 corresponds to input channel
0, bit 01 corresponds to input channel 1, and so on.
Write
Word 0
Bits 08-15 (1017)
Configure select bits (C)
for individual channels - Bit 08 corresponds to input
channel 0, bit 09 corresponds to input channel 1, and so on. Refer to Range Bit
Selections.