Rockwell Automation Publication 1788-UM059B-EN-P - September 2015
Chapter 3
Install the 1788-EN2DNR Linking Device
Set the DeviceNet Node
Address and Baud Rate
Two methods can be used to set the DeviceNet node address and the baud rate:
•
Use the node address and baud rate rotary switches on the linking device
•
Use RSNetWorx for DeviceNet software
Set the DeviceNet Node Address and Baud Rate by Using the
Rotary Switches
Set the desired node address and baud rate using the rotary switches on the
device, according to these tables.
Set the DeviceNet Node Address and Baud Rate by Using RSNetWorx
for DeviceNet Software
Set the DeviceNet Node Address and Baud Rate on page 46
for information
about using RSNetWorx software to set node address and baud rate.
Set the Linking Device
IP Address
Four methods can be used to set the linking device IP address:
•
Use the IP address rotary switches on the linking device
•
Use the DHCP protocol
•
Use RSLinx software
•
Use the web pages of the linking device
Switch
Node Address
00 - 63
DeviceNet node address
Other value
Node address selected via RSNetWorx
software
Switch
Baud Rate
0
125 kbps
1
250 kbps
2
500 kbps
Other value
Baud rate selected via RSNetWorx
software
Содержание 1788-EN2DNR
Страница 1: ...EtherNet IP to DeviceNet Linking Device Catalog Numbers 1788 EN2DNR 1788 EN2DNROM User Manual...
Страница 4: ...4 Rockwell Automation Publication 1788 UM059B EN P September 2015 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 1788 UM059B EN P August 2015 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 1788 UM059B EN P September 2015 Preface Notes...
Страница 62: ...62 Rockwell Automation Publication 1788 UM059B EN P September 2015 Chapter 5 USB Cable Notes...
Страница 66: ...66 Rockwell Automation Publication 1788 UM059B EN P September 2015 Chapter 6 SD Card Notes...
Страница 77: ......