7"8$9/
!"#$%&'()
5–12
Note: When using the 1785-KE in this application, you must set each
slave 1785-KE to Remote Mode by correctly setting the Local/Remote
Option switch (see Chapter 3 for details).
You may wish to refer to Appendix D “Interprocessor Addressing” for
more background information on addressing PLC-5’s from PLC-2’s.
Setting the 1785-KE’s Node Address
When used in a RS-232 multidrop application, the 1785-KE has each of
the following:
a Data Highway Plus address on the Data Highway Plus link
a slave node address on the master-slave multidrop network
A single 1785-KE node address, used on both links, is selected by setting
the appropriate switches on Switch Assembly SW-2 (see Chapter 3 for
details on setting option switches).
The valid range of slave addresses on the multidrop network is 001-376
octal (010-077 and 110-376 octal when a 1771-KGM is used as the
master). The valid range of addresses on Data Highway Plus is 00-77 octal.
Figure 5.4 below shows Switch Assembly SW-2