H,410**+,<)1=/)$IJK#LM
!"#$%&'()
3–5
Switch assembly SW-2 is for setting the Data Highway Plus node address
of the 1785-KE (figure 3.3).
?./A'&()E)
7&%%.+/(79.%8"(:,,&;<-=(7L4J
As seen in the figure, SW-2 represents 3 octal digits; Octal Digit 0, Digit 1,
and Digit 2.
Octal Digit 0
Octal Digit 0 (Switches 1 and 2) should be set to 0 (DWN DWN).
Octal Digits 1 and 2 (Data Highway Plus Node Address)
Octal Digits 1 and 2 are used to set a Data Highway Plus node address for
the 1785-KE module. The node address is an encoded 2 digit octal number
that identifies the 1785-KE module as a unique node on Data Highway
Plus. Valid Data Highway Plus addresses for the 1785-KE module are
00 to 77 octal.
Octal Digit 1 (switches 3, 4, 5) is used to set the most significant octal digit
(0-7) of the Data Highway Plus node address.
Octal Digit 2 (switches 6, 7, 8) is used to set the least significant octal digit
(0-7) of the Data Highway Plus node address.