Chapter 5
Issuing BlockTransfer Commands
5-4
Table 5.A
Host BT Write Error Conditions
Error Mnemonic
Code
Description
SUCCESS
0
The BT Write was successful.
BAD_COMMAND_DATA_LENGTH
26
Command data length exceeds maximum.
BT_BAD_ADDRESS
27
Logical rack address or slot address is out of range.
BT_BAD_ADDRESS_NOT_IN_SCAN_LIST
28
BT address is not in scan list.
BT_BAD_DATA_LENGTH
29
More than 63 words were specified.
TOO_MANY_REQUESTS_FOR_MODULE
30
This module already has a BT in progress.
BT_QUEUE_FULL
31
Already 64 BT requests pending.
BT_REQUEST_TIMEOUT
36
BT exchange between scanner and adapter did not complete within 4 seconds.
USER_MODULE_REQUEST_TYPE_MISMATCH
38
Host requested a write, module responded with a read request.
USER_MODULE_LENGTH_MISMATCH
39
Length mismatch between what the scanner requested and the adapter requested.
MODULE_REQUESTED_TOO_MUCH_DATA
40
Module requested more data than host supplied.
1
MODULE_IN_FAULT_GROUP_REQUESTED_BT
50
A BT Write was requested for a module that is in a faulted group.
1
This condition applies only to Adapter Decide Length.
instructs the scanner to perform a
Host BT Write
.