Allen-Bradley 1606-XLS960E-3 Скачать руководство пользователя страница 25

All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM005A-EN-P - February 2014

25

Bulletin 1606 Switched Mode Power Supplies

25.7. Parallel Use to Increase Output Power 

Power supplies from the 16060-XLS series can be paralleled to increase
the output power. The output voltage shall be adjusted to the same value 
(±100mV) in “Single use” mode with the same load conditions on all units, or 
the units can be left with the factory settings. After the adjustments, the 
jumper on the front of the unit shall be moved from “Single use” to 
“Parallel use” in order to achieve lo ad sharing. The “Parallel use” mode 
regulates the output voltage in such a manner that the voltage at no load is 
approx. 4% higher than at nominal load. See also section 6. If no jumper is 
plugged in, the unit is in “Single use” mode. Factory setting is also “Single 
use” mode.  

Unit B

-

+

Load

+

-

AC

DC

AC

DC

-

+

Unit A

If more than three units are connected in parallel, a fuse or circuit breaker with a rating of 50A or 63A is required on 
each output. Alternatively, a diode or redundancy module can also be utilized. 
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power 
supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard 
mounting orientation (terminals on the bottom of the unit) or in any other condition where derating of the output 
current is required (e.g. altitude, above 60°C, …). 
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 
 

25.8. Parallel Use for Redundancy 

Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a 
certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two 
power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is 
automatically able to support the load current without any interruption. Redundant systems for a higher power 
demand are usually built in a N+1 method. E.g. five power supplies, each rated for 40A are paralleled to build a 160A 
redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also 
section 25.7. 

Please note:

 This simple way to build a redundant system does not cover failures such as an internal short circuit in 

the secondary side of the power supply. In such a case, the defective unit becomes a load for the other power supplies 
and the output voltage can not be maintained any more. This can be avoided by using redundancy modules that include 
have decoupling devices (diodes or mosfets). Further information and wiring configurations are provided in 
section 24-3. 
Recommendations for building redundant power systems: 
a)

Use separate input fuses for each

 

power supply. A separate source for each supply when possible increases the 

reliability of the redundant system. 

b)

Set the power supply into “Parallel Use” mode. 

c)

Monitor the individual power supply units. Therefore, use the DC-OK relay contact of the 1606 power supply. 

d)

It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting. 

Содержание 1606-XLS960E-3

Страница 1: ...y and Abbreviations e g a P e g a P 1 Intended Use 3 2 Installation Requirements 3 3 AC Input 4 4 Input Inrush Current 5 5 DC Input 5 6 Output 6 7 Hold up Time 8 8 DC OK Relay Contact 9 9 Shut down In...

Страница 2: ...saves space and money High immunity to transients and power surges as well as low electromagnetic emission allow the use of these power supplies in nearly every environment The integrated output powe...

Страница 3: ...25 13 This device is designed for convection cooling and does not require an external fan Do not obstruct airflow and do not cover ventilation grid e g cable conduits by more than 30 Keep the followin...

Страница 4: ...ymmetrical phase voltages see Fig 3 3 Power factor typ 0 88 0 90 at 24V 40A see Fig 3 4 Start up delay typ 500ms 600ms see Fig 3 2 Rise time typ 35ms 35ms at 24V 40A resistive load 0mF see Fig 3 2 typ...

Страница 5: ...input current is usually smaller than the steady state input current 3AC 400V 3AC 480V Inrush current max 6Apeak 6Apeak over entire temperature range typ 4 5Apeak 4 5Apeak over entire temperature ran...

Страница 6: ...put power nom 960W continuously available at 24 28V nom 1440W short term available BonusPower at 24 28V BonusPower time typ 4s duration until the output voltage dips see Fig 6 3 BonusPower recovery ti...

Страница 7: ...Current Factory setting A B A B A B Short term 4s BonusPower Continuously available Fig 6 3 Bonus time vs output power Fig 6 4 Dynamic overcurrent capability typ max Bonus Time 0 100 120 130 140 150 1...

Страница 8: ...0ms at 24V 20A see Fig 7 1 min 40ms 40ms at 24V 20A see Fig 7 1 typ 25ms 25ms at 24V 40A see Fig 7 1 min 20ms 20ms at 24V 40A see Fig 7 1 Curves and figures for operation on only 2 legs of a 3 phase s...

Страница 9: ...d Isolation voltage See Dielectric Strength table in section 21 Fig 8 1 DC ok relay contact behavior 250ms 0 9 VADJ 1ms 10 open VOUT VADJ open closed closed 1ms 9 Shut down Input This feature allows a...

Страница 10: ...a Logging A protected microcontroller inside the power supply acquires and stores operating data during the life of the unit The data can be downloaded with a small tool and special software by Rockwe...

Страница 11: ...r 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest of the time Efficiencies when using o...

Страница 12: ...the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices MTBF st...

Страница 13: ...d to open the spring Recommended tightening torque 1Nm 9lb in 2 3Nm 20 5lb in Not applicable Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C f...

Страница 14: ...ter Open the flap to set the output voltage Factory set 24 1V at full output current Single Use mode E DC OK LED green On when the voltage on the output terminals is 90 of the adjusted output voltage...

Страница 15: ...s Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0Vac 5000ms Criterion C Voltage sags SEMI F47 0706 dips on two phases according to section 7 2 of the SEMI F47 sta...

Страница 16: ...8 2 27 Altitude 0 to 2000m 0 to 6 560ft no restrictions 2000 to 6000m 6 560 to 20 000ft reduce output power or ambient temperature see Fig 18 2 IEC 62103 EN 50178 overvoltage category II Altitude de r...

Страница 17: ...mm e g screws small parts Over temperature protection yes Output shut down with automatic restart Input transient protection MOV Metal Oxide Varistor Internal input fuse included not user replaceable...

Страница 18: ...4 1 we recommend that either the pole the pole or any other part of the output circuit shall be connected to the protective earth system This helps to avoid situations in which a load starts unexpecte...

Страница 19: ...14 19 Bulletin 1606 Switched Mode Power Supplies 23 Physical Dimensions and Weight Weight 1500g 3 3lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN...

Страница 20: ...d circuit at any given point Buffer units can be added in parallel to increase the output ampacity or the hold up time 1606 XLSRED80 Redundancy Module Input 1 Input 2 Output 24V 40A Load Failure Monit...

Страница 21: ...al shut down after a period of time Use the maximum duty cycle curve Fig 25 2 to check if the average output current is below the nominal current d The duty cycle must be below 0 75 Fig 25 1 Repetitiv...

Страница 22: ...t circuits The extra current peak current is supplied by the power converter and the built in large sized output capacitors of the power supply The capacitors get discharged during such an event which...

Страница 23: ...e EMC performance hold up time losses and output ripple differ from a three phase operation Therefore check suitability of your individual application Such use is not included in the UL approval Addit...

Страница 24: ...ircuits If the ampere value and the characteristics of the MCB are adapted to the wire size that is used the wiring is considered as thermally safe whether the MCB opens or not To avoid voltage dips a...

Страница 25: ...t leakage current EMI inrush current harmonics will increase when using multiple power supplies 25 8 Parallel Use for Redundancy Power supplies can be paralleled for redundancy to gain higher system a...

Страница 26: ...nd Capacitive Loads The unit is designed to supply any kind of load including capacitive and inductive loads 25 11 Back feeding Loads Loads such as decelerating motors and inductors can feed voltage b...

Страница 27: ...Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 25 10 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Output Current 0 10 20 3...

Страница 28: ...your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility Ho...

Отзывы: