All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

12

Rockwell Automation Publication 1606-RM005A-EN-P - February 2014

Bulletin 1606 Switched Mode Power Supplies

 

13. Reliability 

 

 3AC 

400V

 

3AC 480V

 

 

Calculated lifetime expectancy

*)

 314 

000h

*)

 294 

000h

*)

 

at 24V, 20A and 25°C 

 

111 000h 

104 000h 

at 24V, 20A and 40°C 

 179 

000h

*)

 174 

000h

*)

 

at 24V, 40A and 25°C 

 

63 000h 

62 000h 

at 24V, 40A and 40°C 

MTBF

**)

  SN 29500, IEC 61709 

375 000h 

369 000h 

at 24V, 40A and 40°C 

 

685 000h 

678 000h 

at 24V, 40A and 25°C 

MTBF

**)

  MIL HDBK 217F 

158 000h 

157 000h 

at 24V, 40A and 40°C; Ground Benign GB40 

 

211 000h 

210 000h 

at 24V, 40A and 25°C; Ground Benign GB25 

*)   The 

calculated lifetime expectancy

 shown in the table indicates the minimum operating hours (service life) and is determined by the 

lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according 
to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 
years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices. 

**) 

MTBF

 stands for 

M

ean 

T

ime 

B

etween 

F

ailure, which is calculated according to statistical device failures, and indicates reliability of a 

device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 

 

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that 
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it’s impossible to determine if the failing
unit has been running for 50 000h or only for 100h. 

 
 
 

14. Functional Diagram 

 

 

Fig. 14-1

   Functional diagram 

 

 

+

+

-
-

V

OUT

DC-ok

Contact

Output

Over-

Voltage

Protection

PFC

Converter

Input Fuses
Input Filter
Input Rectifier
Inrush Limiter
Transient Filter

Output

Voltage

Regulator

Power

Converter

Output

Filter

DC ok

Relay

Output

Voltage

Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

Overload

LED
DC-ok

LED

L2
L3

L1

Single /

Parallel

Shut-

down

Input

Shut-

down

13

14

15

16

Event Datalogger

 

 
 

Содержание 1606-XLS960E-3

Страница 1: ...y and Abbreviations e g a P e g a P 1 Intended Use 3 2 Installation Requirements 3 3 AC Input 4 4 Input Inrush Current 5 5 DC Input 5 6 Output 6 7 Hold up Time 8 8 DC OK Relay Contact 9 9 Shut down In...

Страница 2: ...saves space and money High immunity to transients and power surges as well as low electromagnetic emission allow the use of these power supplies in nearly every environment The integrated output powe...

Страница 3: ...25 13 This device is designed for convection cooling and does not require an external fan Do not obstruct airflow and do not cover ventilation grid e g cable conduits by more than 30 Keep the followin...

Страница 4: ...ymmetrical phase voltages see Fig 3 3 Power factor typ 0 88 0 90 at 24V 40A see Fig 3 4 Start up delay typ 500ms 600ms see Fig 3 2 Rise time typ 35ms 35ms at 24V 40A resistive load 0mF see Fig 3 2 typ...

Страница 5: ...input current is usually smaller than the steady state input current 3AC 400V 3AC 480V Inrush current max 6Apeak 6Apeak over entire temperature range typ 4 5Apeak 4 5Apeak over entire temperature ran...

Страница 6: ...put power nom 960W continuously available at 24 28V nom 1440W short term available BonusPower at 24 28V BonusPower time typ 4s duration until the output voltage dips see Fig 6 3 BonusPower recovery ti...

Страница 7: ...Current Factory setting A B A B A B Short term 4s BonusPower Continuously available Fig 6 3 Bonus time vs output power Fig 6 4 Dynamic overcurrent capability typ max Bonus Time 0 100 120 130 140 150 1...

Страница 8: ...0ms at 24V 20A see Fig 7 1 min 40ms 40ms at 24V 20A see Fig 7 1 typ 25ms 25ms at 24V 40A see Fig 7 1 min 20ms 20ms at 24V 40A see Fig 7 1 Curves and figures for operation on only 2 legs of a 3 phase s...

Страница 9: ...d Isolation voltage See Dielectric Strength table in section 21 Fig 8 1 DC ok relay contact behavior 250ms 0 9 VADJ 1ms 10 open VOUT VADJ open closed closed 1ms 9 Shut down Input This feature allows a...

Страница 10: ...a Logging A protected microcontroller inside the power supply acquires and stores operating data during the life of the unit The data can be downloaded with a small tool and special software by Rockwe...

Страница 11: ...r 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest of the time Efficiencies when using o...

Страница 12: ...the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices MTBF st...

Страница 13: ...d to open the spring Recommended tightening torque 1Nm 9lb in 2 3Nm 20 5lb in Not applicable Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C f...

Страница 14: ...ter Open the flap to set the output voltage Factory set 24 1V at full output current Single Use mode E DC OK LED green On when the voltage on the output terminals is 90 of the adjusted output voltage...

Страница 15: ...s Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0Vac 5000ms Criterion C Voltage sags SEMI F47 0706 dips on two phases according to section 7 2 of the SEMI F47 sta...

Страница 16: ...8 2 27 Altitude 0 to 2000m 0 to 6 560ft no restrictions 2000 to 6000m 6 560 to 20 000ft reduce output power or ambient temperature see Fig 18 2 IEC 62103 EN 50178 overvoltage category II Altitude de r...

Страница 17: ...mm e g screws small parts Over temperature protection yes Output shut down with automatic restart Input transient protection MOV Metal Oxide Varistor Internal input fuse included not user replaceable...

Страница 18: ...4 1 we recommend that either the pole the pole or any other part of the output circuit shall be connected to the protective earth system This helps to avoid situations in which a load starts unexpecte...

Страница 19: ...14 19 Bulletin 1606 Switched Mode Power Supplies 23 Physical Dimensions and Weight Weight 1500g 3 3lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN...

Страница 20: ...d circuit at any given point Buffer units can be added in parallel to increase the output ampacity or the hold up time 1606 XLSRED80 Redundancy Module Input 1 Input 2 Output 24V 40A Load Failure Monit...

Страница 21: ...al shut down after a period of time Use the maximum duty cycle curve Fig 25 2 to check if the average output current is below the nominal current d The duty cycle must be below 0 75 Fig 25 1 Repetitiv...

Страница 22: ...t circuits The extra current peak current is supplied by the power converter and the built in large sized output capacitors of the power supply The capacitors get discharged during such an event which...

Страница 23: ...e EMC performance hold up time losses and output ripple differ from a three phase operation Therefore check suitability of your individual application Such use is not included in the UL approval Addit...

Страница 24: ...ircuits If the ampere value and the characteristics of the MCB are adapted to the wire size that is used the wiring is considered as thermally safe whether the MCB opens or not To avoid voltage dips a...

Страница 25: ...t leakage current EMI inrush current harmonics will increase when using multiple power supplies 25 8 Parallel Use for Redundancy Power supplies can be paralleled for redundancy to gain higher system a...

Страница 26: ...nd Capacitive Loads The unit is designed to supply any kind of load including capacitive and inductive loads 25 11 Back feeding Loads Loads such as decelerating motors and inductors can feed voltage b...

Страница 27: ...Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 25 10 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Output Current 0 10 20 3...

Страница 28: ...your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility Ho...

Отзывы: