TROUBLESHOOTING

Sensor will not set up 

upon intial powering

Improper input voltage

Check terminals 1 and 2 for proper voltage (12 – 24 VAC / VDC  

± 10%).

Sensor is in detection

Ensure field of detection is clear during set-up and all lenses are installed 

on sensor.  If detection is encountered upon initial set-up, the HMSS will 

continuously flash green at ±2 Hz.  

Permanent stationary objects are extremely close to the sensor.  Ensure 

that the detection field clear and the sensor is mounted properly (using the 

HMSS Spacer, if necessary). 

Potential interferences from 

high-intensity lighting

Ensure no high-intensity lighting is in the immediate area of the sensor.

Change to a different frequency.

Data type mismatch (old/

new)

Verify that the data matches type LO21 or EDPS.

Door will not open once 

set-up is complete

Sensor is in detection (red 

LED is on)

Verify no changes in detection field made since set-up.  If permanent 

changes have occurred, launch a new set-up and re-test door (CAUTION: 

THERE MAY BE NO SAFETY ON THE DOOR WHEN THIS TEST IS 

PERFORMED).

Improper wiring

Remove output wires from the sensor.  For controls using N.C. circuits, twist
together the relay wires.  
Activate the door control.  If the door opens, the fault exists with sensor 

or related wiring.  If door does not open, the fault may exist with the door 

control or its related wiring.

Safety beams are in 

detection

Disconnect green and blue wires from LO21 to the door control safety 

and common terminals.  If door opens when triggered, fault lies within 

the lockout safety beam set, or possibly with the LO21.  Refer to the LO21 

troubleshooting procedures in the respective manual.

Improper relay output 

configuration

Ensure proper relay output setting.

Sensor repeatedly  

re-Learns environment 

with each door position

Improper data from lockout 

device

1) Allow door to open in automatic mode. Unlock sensor and launch a set-

up by pressing the Set-Up key, followed by the number 2. If the sensor LED 

returns to red and does not begin flashing green, improper data exists. 
2) If unsuccessful, allow the door to close.   Unlock sensor and launch a set-

up by pressing the Set-Up key, followed by the number 2. If the sensor LED 

flashes green, the lockout module needs replaced.
Refer to respective lockout User’s Guide for troubleshooting.

Data polarity at sensor is 

incorrect

Verify that the negative wire from the lockout (white) is connected to 

terminal 6, and the red/white wire from the lockout is connected at terminal 

7.

HELPFUL HINT:  

If faulty data is suspected, simply power the door to the 

open position (by activation OR with the use of a “hold open” switch).  

While the door is open, unlock the sensor and press the Set-Up key, 

followed by the number 2.  If the sensor LED returns to red and does not 

begin flashing green, improper data exists.  Refer to respective lockout 

User’s Guide for troubleshooting.

Sensor is not reacting to 

remote control

RC batteries are dead

Replace batteries.

Too much distance between 

sensor and RC

Move closer to sensor during programming.

Data type mismatch (old/

new)

Verify data matches type LO21 or EDPS.

Unknown

Attempt manual programming procedure (page 7).

Visible Monitoring 

Indication LED does 

not flash

Monitoring installation / 

set-up error

Verify monitoring is active in door control (active low).

Sensor malfunction

Replace sensor.

Monitoring DIP switch 

is OFF

Verify DIP switch poisiton (must be switched to the left).

Visible Monitoring 

Indication LED flashes 

continuously

The DIP switch is set to ON

Place the monitoring DIP switch to the right (OFF).

Содержание 8310-877

Страница 1: ...10 Power supply 12 24 VAC VDC 10 Monitoring request input 12 30 VDC required polarity sensitive min pulse width 10 ms active low Frequency 50 60 Hz Output max voltage at contacts 60 VDC 125 VAC max c...

Страница 2: ...from midpoint of each sensor SIMULTANEOUS PAIR APPLICATIONS Sensor must be mounted at center of door opening The door control unit and the header cover profile must be correctly grounded Only trained...

Страница 3: ...esired location Drill pilot holes for mounting and wire passage Partially drill the 2 mounting screws into the pilot holes Remove the left end cap of the Spacer for wiring harness routing Slide extrus...

Страница 4: ...crews provided with the kit Slide the circuit board back into the extrusion ANGLE ADJUSTMENTS MOUNTING TO SPACER REPLACE THE CIRCUIT BOARD MECHANICAL INSTALLATION cont 3 2 2 1 1 0 Should only be used...

Страница 5: ...s set to off see below Once wired feed the free end of the cable through the wire passage hole page 3 step 8 and into the header Pull the cable completely through and route it to the location of the a...

Страница 6: ...green until set up is successful in door closed position 1 Activate the door to the fully open position LED will flash green again and the sensor will execute a door open set up 1 2 NOTES 1 If the do...

Страница 7: ...00 default code Sensor will unlock with one press of UNLOCK key when set to 0000 DOOR CONTROL 1 Normal LED in normal mode 2 Door permanently open red LED on 3 Door permanently closed red LED off INFRA...

Страница 8: ...me 0 30 seconds 1 1 minute 2 2 minutes 3 3 minutes 4 5 minutes 5 7 minutes 6 10 minutes 7 15 minutes 8 10 seonds 9 Infinity no learn Pattern Width 1 Wide closed door 2 Middle open door 3 Asymm left na...

Страница 9: ...e NOTES Pressing PB1 will toggle between parameters Pressing PB2 will toggle between range of adjustments for that particular parameter The value returns to the lowest setting when PB2 is pressed agai...

Страница 10: ...5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 1...

Страница 11: ...roper relay output configuration Ensure proper relay output setting Sensor repeatedly re Learns environment with each door position Improper data from lockout device 1 Allow door to open in automatic...

Страница 12: ...ADM certified for pedestrian doors IDA certified for doors gates and factory trained for the type of door gate system Installers and service personnel are responsible for executing a risk assessment f...

Отзывы: