24
Annex
Annex
Manual ADQ-22/23-Serie Rev. 1.1
Element
Condition
Specification
Output level
U
OH
11..35 V
Output current
U
O
= typ. 24 VDC
I
O
max. 0.6 A per channel (parallel connection possible)
DC short-circuit current
VEXT_DO = 24 VDC
R
L
= 10 mΩ
min. 0.7 A; max. 1.7 A
Undervoltage cut-off
VEXT_DO
min. 7 V/max. 10.5 V, Restart at max. 11 V,
hysteresis: typ. 0.5 V
Overvoltage protection
VEXT_DO
min. 47 VDC
Dissipation energy with
inductive load
per channel
max. 1 Joule
Resistance with active
output
I
O
= 0.5 A; T
A
= 25°C
typ. 150 mΩ, max. 200 mΩ
Leakage current with
inactive channel
typ. 5 µA, max. 30 µA
Cut-off current with
inductive loads
typ. 1.4 A
t
on
(switch-on time)
R
L
= 47Ω, up to 90% U
O
typ. 64 µs; max. 120 µs
t
off
(switch-off time)
R
L
= 47Ω, up to 10% U
O
typ. 89 µs; max. 170 μs
dUO/dt(on) (slope when
switching on)
von 10..30% U
O
,
R
L
= 47Ω,
VEXT_DO = 15V
typ. 1 V/μs; max. 2 V/μs
dUO/dt(off) (slope when
switching off)
from 70..40% U
O
,
R
L
= 47Ω,
VEXT_DO = 15V
typ. 1 V/μs; max. 2 V/μs
Switch-off temperature
min. 135 °C
Thermal hysteresis
10°K
Operable
Simple output, streaming operation
Monitoring
per channel
IRQ in case of thermal overload
Streaming operation
per channel
max. 1 kS/s (via software timer)
External supply
VEXT_DO
11..35 VDC; typ. 24 VDC for control technology
Ground reference
GND_EXT (isolated from PC ground GND_PC)
Relay
Conditions: T
A
= 25°C
Element
Condition
Specification
Anzahl
8 change-over relay (type C)
Typ
NAIS APE3005 or compatible
Dauerbelastbarkeit
Direct current
max. 35 VDC/1 A
Alternating current
max. 35 VAC/1 A
Widerstand
per channel
typ. 200 mΩ; max. 250 mΩ
Isolationswiderstand
min. 103 MΩ at 500 VDC