background image

16

17

Drainpipe Installation

The drainpipe is used to drain water from the 
unit. Improper installation may cause unit and 
property damage. 

• 

Insulate all piping to prevent condensation, 

which could lead to water damage. 

• 

If the drainpipe is bent or installed 

incorrectly, water may leak and cause a 

malfunction of the water- level switch.  

• 

In HEAT mode, the outdoor unit will 

discharge water. Ensure that the drain hose 

is placed in an appropriate area to avoid 

water damage and slippage due to frozen 

drain water.    

• 

DO NOT

 pull the drainpipe forcefully as this 

could cause it to disconnect.

NOTE ON PURCHASING PIPES

This installation requires a polyethylene tube 

(outside diameter = 3.7-3.9cm, inside diameter 

= 3.2cm), which can be obtained at your local 

hardware store or from your dealer.   

Indoor Drainpipe Installation

1.

 

Make sure the drain pipe is connected to the 
outdoor side downward.

2.

 

The hard polyvinyl chloride(PVC)plastic pipe 

(external diameter 26 mm) sold in the market 

is suitable for the attached soft drain pipe.

4. After the Drain Pipe has been connected, 

please check if the water drains out of the 

pipe efficiently and has no leakage.

5. Refrigerant Pipe and Drain Pipe should be 

heat-insulated to avoid condensing and 

water-dropping later on.

3. Please connect the Soft Drain Pipe with the 

Drain Pipe, then fix it with band; if you have 

to connect the Drain Pipe indoors, to avoid 
condensing caused by air intake, you must 
cover the pipe with heat-insulation material 

(polyethylene with Specific Gravity of 0.03, at 
least 9 mm in thickness), and use Glue Band 
to fix it.

Fig. 6.1

6. Using a 65-mm (2.5”) core drill, drill a hole

in the wall. Make sure that the hole is
drilled at a slight downward angle, so that
the outdoor end of the hole is lower than

the indoor end by about 1cm (0.4”). 

This will ensure proper water drainage
(See Fig. 6.2).  Place the protective wall cuff 
in the hole. This protects the edges of the 

hole and will help seal it when you finish the 

installation process.       

Wall

Indoor

Outdoor

� 0.5~1cm 
/ 0.2~0.4 inch 

 

Fig. 6.2

NOTE:

 When drilling the wall hole, make 

sure to avoid wires, plumbing, and other 
sensitive components.

7. Pass the drain hose through the wall hole. 

Make sure the water drains to a 
safe location where it will not cause water 
damage or a slipping hazard.   

NOTE:

 The drainpipe outlet should be 

at least 5cm (1.9”) above the ground. If it 
touches the ground, the unit may become 
blocked and malfunction. If you discharge 
the water directly into a sewer, make sure 
that the drain has a U or S pipe to catch 
odors that might otherwise come back 
into the house.

Drain pipe 

Drain pipe 

Glue

Band for covering the pipe

 CAUTION

Refrigerant Piping Connection

Safety Precautions

• 

All field piping must be completed by a 

 

licensed technician and must comply with 
the local and national regulations. 

•  When the air conditioner is installed in a 

 

small room, measures must be taken to 
prevent the refrigerant concentration in 
the room from exceeding the safety limit 
in the event of refrigerant leakage. If the 
refrigerant leaks and its concentration 
exceeds its proper limit, hazards due to 
lack of oxygen may result.     

•  When installing the refrigeration system, 

 

 

 

ensure that air, dust, moisture or foreign 
substances do not enter the refrigerant 
circuit. Contamination in the system may 
cause poor operating capacity, high 
pressure in the refrigeration cycle, 
explosion or injury.     

 

•  Ventilate the area immediately if there is

 

   

refrigerant leakage during the installation. 
Leaked refrigerant gas is both toxic and 

flammable. Ensu

re there is no refrigerant 

leakage after completing the installation 
work.    

Refrigerant Piping Connection Instructions

• 

The branching pipe must be installed 
horizontally. An angle of mor

e than 10° 

may cause malfunction. 

• 

DO NOT

 install the connecting pipe until 

both indoor and outdoor units have been 
installed. 

 

• 

Insulate both the gas and liquid piping to 
prevent water leakage. 

Step1: Cut pipes

When preparing refrigerant pipes, take extra 
car

e to cut and flare them p

roperly. This will 

ensur

e efficient operation and minimize the 

need for future maintenance.   

1.

 

Measure the distance between 
the indoor and outdoor units. 

2.

 

Using a pipe cutter, cut the pipe a little 
longer than the measured distance. 

DO NOT

 deform pipe while cutting. 

Be extra ca

reful not to damage, dent, 

or deform the pipe while cutting. This will 
drastically r

educe the heating efficiency 

of the unit. 

 

1. Make sur

e that the pipe is cut at a perfect 90° 

angle. Refer to Fig. 7.1 for examples of bad cuts 

Oblique

Rough

Warped

90°

Fig. 7.1

Step 2: Remove burrs.

Burrs can a

ffect the air-tight seal of refrigerant 

piping connection. They must be completely 
removed. 

1. Hold the pipe at a downward angle to 

prevent burrs from falling into the pipe. 

2. Using a reamer or deburring tool, remove 

all burrs from the cut section of the pipe. 

Pipe

Reamer

Point down

Fig. 7.2

 

WARNING

 CAUTION

 

CAUTION

Содержание FHA-H54R410INV9

Страница 1: ...FHA H54R410INV9 FHA H70R410INV9 FHA H54R410INV9 FHA H70R410INV9 Installation Manual Floor Standing Type AIR CONDITIONERS...

Страница 2: ...ipe Installation 16 Table of Contents Table of Contents Installation Manual Indoor Unit Installation 09 Installation Overview 08 1 2 5 3 4 6 Refrigerant Piping Connection 17 A Refrigerant Piping Conne...

Страница 3: ...y combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit it may cause re Do not operate your air condit...

Страница 4: ...checked for leaks proper record keeping of all checks is strongly recommended Accessories The air conditioning system comes with the following accessories Use all of the installation parts and access...

Страница 5: ...25 Indoor Unit Parts Fig 4 1 1 7 8 9 10 2 3 4 5 6 Indoor Unit Installation Air outlet Operation panel Horizontal air ow control louver Vertical air ow control louver Air inlet 2 sides Drain pipe vent...

Страница 6: ...tape and any components screw bolt xing hole Air inlet Grid 2 Open the two boxes for storing the remote control found on either side of the indoor unit then undo the screws on the operation panel 3 U...

Страница 7: ...le position on back side Pipe wire hole position on the bottom Refrigerant drain Pipe hole Refrigerant drain Pipe hole First remove the metal Then attach the ratproof board into the hole ratproof boar...

Страница 8: ...oor unit Seal Fig 5 5 Notes On Drilling Hole In Wall You must drill a hole in the wall for the refrigerant piping and the signal cable that will connect the indoor and outdoor units 1 Determine the lo...

Страница 9: ...9 above the ground If it touches the ground the unit may become blocked and malfunction If you discharge the water directly into a sewer make sure that the drain has a U or S pipe to catch odors that...

Страница 10: ...the torque values in table 7 1 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Pipe gauge Tightening torque Flare dimension A Unit mm Inch Flare sha...

Страница 11: ...n the product Outdoor Unit Wiring Before performing any electrical or wiring work turn off the main power to the system 1 Prepare the cable for connection a You must rst choose the right cable size be...

Страница 12: ...e wrench in a 1 4 counterclockwise turn Listen for gas to exit the system then close the valve after 5 seconds Flare nut Cap Valve body Valve stem Fig 9 2 9 Watch the Pressure Gauge for one minute to...

Страница 13: ...ndoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the drainage system is unimpeded and draining smoothly g Ensure there is no vibration or abno...

Страница 14: ...25 24 1 2 3 4 2 000 5 6...

Страница 15: ...4 1 6 35 8 3 9 52 60 x 0 64 30 x 0 32 15 x 0 16 R22 65 x 0 69 30 x 0 32 x 0 16 15 R410A 23 22 Flare shape 76 1 9 2 9 0 1 40 0 1 0 1 1 2 3 4 5 15 1x105 76 6 5 7 8 1 4 5 9 10 12 7 5 164 5 25 2 1 12 7...

Страница 16: ...Flare shape 3 0 118 PCB T5A 250VAC T3 15A 250VAC 1 H07RN F 8 1 7 18 13 7 16 18 13 14 25 18 12 30 25 10 _ 6 0 75 10 6 1 16 10 1 5 25 16 2 5 32 35 4 45 32 6 _ 5 9 15 U 2 8 1 U 3 U 4 5 6 8 1 1 5 9 15 U...

Страница 17: ...6 4 R0 4 0 8 45 2 90 4 A 9 5 12 7 15 9 19 1 22 23 2 0 91 26 4 1 04 8 4 0 33 13 2 0 52 16 2 0 64 19 2 0 76 23 7 0 93 26 9 1 06 8 7 0 34 13 5 0 53 16 5 0 65 19 7 0 78 20 18 36 35 367 357 47 45 480 459 6...

Страница 18: ...90 1 7 1 10 17 16 3 7 3 9 3 2 0 5 0 4 0 2 1 6 7 1 2 7 1 2 26 3 9 0 03 4 5 65 6 2 5 0 4 1 6 2 7 1 9 5 S U 1 2 90 1 2...

Страница 19: ...404 900 1170 350 590 378 W H 3 5 5 5 5 6 M N P L H L 1 2H L A 1 2H L H L H L A H 9 8 25 11 8 30 L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or more 25 cm 9 8 or more 25 cm 9 8 or more 5 5 5...

Страница 20: ...1 5 2 5 13 12 2 4 6 3 1 2 3 4 57 4 67 67 4 5 8 4 9 4 1 5 2 5 3 5 1 2 3 60cm 23 6 M1 Fig 4 6...

Страница 21: ...10 11 Fig 4 4 Air inlet Grid 11 8 30 78 7 200 2 5 19 7 50 19 7 50 4 2 24 8 629 17 9 455 76 2 1935 18 0 456 4 3 1 2 3 4 5 6 4 4 1 2 1 2 1 M8 2 4 5 3 4 5 1...

Страница 22: ...9 8 L N 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 5 6 7 8 9 10 MC MC 10 14 17 18 21 23 25 4 1...

Страница 23: ...7 6 2 2 1 2 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 2 3 50 5 4 24 5 25 3 9 ST3 9 12 ST 2 9 10 AAA...

Страница 24: ...5 4 1 2 3 4 NEC 5 6 8 7 8 9 10 IEC 11 12 3 13 10 30 RCD 14 15 16 17 18 19 20 21 22 23 24 3 1 1 2...

Страница 25: ...3 2 04 09 10 07 13 13 14 15 16 09 08 1 2 5 3 4 6 17 17 19 20 20 21 7 8 L N 22 22 23 9 10 24 25 11 MC MC...

Отзывы: