background image

18

19

Refrigerant Piping Connection

Refrigerant Piping Connection

Step 3: Flare pipe ends

Pr

oper flaring is essential to achieve an airtight 

seal.

1. After 

r

emoving burrs f

r

om cut pipe, seal 

the ends with PVC tape to p

r

event fo

r

eign 

materials f

r

om entering the pipe. 

2. Sheath the pipe with insulating material.
3. Place fla

r

e nuts on both ends of pipe. 

Make su

r

e they a

r

e facing in the right 

di

r

ection, because you can

t put them on 

or change their di

r

ection after flaring. See 

Fig. 7.3   

Flare nut

Copper pipe

Fig. 7.3

4. Remove PVC tape f

r

om ends of pipe when 

r

eady to perform flaring work.

5. Clamp fla

r

e form on the end of the pipe. 

The end of the pipe must extend beyond 
the fla

r

e form. 

Flare form

Pipe

Fig. 7.4

6. Place flaring tool onto the form.
7.

T

u

r

n the handle of the flaring tool 

clockwise until the pipe is fully fla

r

ed. Fla

re 

the pipe in acco

r

dance with the dimensions 

shown in table 7.1.  

Table 7.1: PIPING EXTENSION BEYOND FLARE 
                 FORM

8. Remove the flaring tool and fla

r

e form, 

then inspect the end of the pipe for cracks 
and even flaring.  

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, 
then connect

 

it to

 

the outdoor

 

unit.

 Y

ou should

 

first connect

 

the low-p

r

essu

r

e pipe, then the 

high-p

r

essu

r

e pipe.  

1. When connecting the fla

r

e nuts, apply a 

thin coat of 

r

efrigeration oil to the fla

r

ed 

ends of the pipes.  

2. Align

 

the cent

er of 

the two

 p

ipes that

 

you

 

will connect.  

Indoor unit tubing

Flare nut

Pipe

Fig. 7.6

3.

T

ighten the fla

r

e nut as tightly as possible 

by hand. 

4. Using a spanne

r

, grip the nut on the unit 

tubing.

5. While firmly gripping the nut, use a to

r

que 

w

r

ench to tighten the fla

r

e nut acco

r

ding 

to the to

r

que values in table 7.1.  

NOTE:

 Use both a spanner and a to

r

que 

w

r

ench when connecting or disconnecting 

pipes to/f

r

om the unit.

  Pipe 
gauge 

Tightening 

to

r

que

Fla

r

e dimension (A) 

(Unit: mm/Inch)

Fla

r

e shape

Min.

Max .

Ø 6.4

R0.4~0.8

45 °

2

90 °      

4

A

Fig. 7.5

Ø 9.5

Ø 12.7

Ø 15.9

Ø 19.1

Ø 22

65-67 N.m 

(663-683 kgf.cm)

23.2/0.91

23.7/0.93

75-85N.m 

(765-867 kgf.cm)

26.4/1.04

26.9/1.06

18-20 N.m 

(183-204 kgf.cm)

8.4/0.33

8.7/0.34

25-26 N.m 

(255-265 kgf.cm)

13.2/0.52

13.5/0.53

35-36 N.m 

(357-367 kgf.cm)

16.2/0.64

16.5/0.65

45-47 N.m 

(459-480 kgf.cm)

19.2/0.76

19.7/0.78

Fig. 7.7

• 

Ensu

r

e to wrap insulation a

r

ound the piping. 

Di

r

ect contact with the ba

r

e piping may 

r

esult in bu

r

ns or f

r

ostbite.  

• 

Make su

r

e the pipe is p

r

operly connected. 

Over tightening may damage the bell mouth 
and under tightening may lead to leakage.   

NOTES ON MINIMUM BEND RADIUS 

Ca

r

efully bend the tubing in the middle 

acco

r

ding to the diagram below. 

DO NOT

 

bend the tubing mo

r

e than 90° or mo

r

e than 

3 times.  

 

 

Be

nd th

e p

ip

e

 with thu

m

b

min-radius 

10

cm (3.9”)

Fig. 7.8

6. After connecting the copper pipes to the 

indoor unit, wrap the power cable, signal 
cable and the piping together with 
binding tape.  

NOTE: DO NOT intertwine signal cable with 
other wi

r

es. While bundling these items 

togethe

r

, do not intertwine or c

r

oss the signal 

cable with any other wiring. 

 

Check to make su

r

e the

r

e is no 

r

efrigerant 

leak after completing the installation work. 
If the

r

e is a 

r

efrigerant leak, ventilate the a

r

ea 

immediately and evacuate the system (

refer 

to the Air Evacuation section of this manual).    

7. Thread this pipeline th

r

ough the wall and 

connect it to the outdoor unit.  

8. Insulate all the piping, including the valves 

of the outdoor unit.  

9. Open the stop valves of the outdoor unit 

to start the flow of the 

r

efrigerant between 

the indoor and outdoor unit.  

 CAUTION

 CAUTION

Содержание FHA-H54R410INV9

Страница 1: ...FHA H54R410INV9 FHA H70R410INV9 FHA H54R410INV9 FHA H70R410INV9 Installation Manual Floor Standing Type AIR CONDITIONERS...

Страница 2: ...ipe Installation 16 Table of Contents Table of Contents Installation Manual Indoor Unit Installation 09 Installation Overview 08 1 2 5 3 4 6 Refrigerant Piping Connection 17 A Refrigerant Piping Conne...

Страница 3: ...y combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit it may cause re Do not operate your air condit...

Страница 4: ...checked for leaks proper record keeping of all checks is strongly recommended Accessories The air conditioning system comes with the following accessories Use all of the installation parts and access...

Страница 5: ...25 Indoor Unit Parts Fig 4 1 1 7 8 9 10 2 3 4 5 6 Indoor Unit Installation Air outlet Operation panel Horizontal air ow control louver Vertical air ow control louver Air inlet 2 sides Drain pipe vent...

Страница 6: ...tape and any components screw bolt xing hole Air inlet Grid 2 Open the two boxes for storing the remote control found on either side of the indoor unit then undo the screws on the operation panel 3 U...

Страница 7: ...le position on back side Pipe wire hole position on the bottom Refrigerant drain Pipe hole Refrigerant drain Pipe hole First remove the metal Then attach the ratproof board into the hole ratproof boar...

Страница 8: ...oor unit Seal Fig 5 5 Notes On Drilling Hole In Wall You must drill a hole in the wall for the refrigerant piping and the signal cable that will connect the indoor and outdoor units 1 Determine the lo...

Страница 9: ...9 above the ground If it touches the ground the unit may become blocked and malfunction If you discharge the water directly into a sewer make sure that the drain has a U or S pipe to catch odors that...

Страница 10: ...the torque values in table 7 1 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Pipe gauge Tightening torque Flare dimension A Unit mm Inch Flare sha...

Страница 11: ...n the product Outdoor Unit Wiring Before performing any electrical or wiring work turn off the main power to the system 1 Prepare the cable for connection a You must rst choose the right cable size be...

Страница 12: ...e wrench in a 1 4 counterclockwise turn Listen for gas to exit the system then close the valve after 5 seconds Flare nut Cap Valve body Valve stem Fig 9 2 9 Watch the Pressure Gauge for one minute to...

Страница 13: ...ndoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the drainage system is unimpeded and draining smoothly g Ensure there is no vibration or abno...

Страница 14: ...25 24 1 2 3 4 2 000 5 6...

Страница 15: ...4 1 6 35 8 3 9 52 60 x 0 64 30 x 0 32 15 x 0 16 R22 65 x 0 69 30 x 0 32 x 0 16 15 R410A 23 22 Flare shape 76 1 9 2 9 0 1 40 0 1 0 1 1 2 3 4 5 15 1x105 76 6 5 7 8 1 4 5 9 10 12 7 5 164 5 25 2 1 12 7...

Страница 16: ...Flare shape 3 0 118 PCB T5A 250VAC T3 15A 250VAC 1 H07RN F 8 1 7 18 13 7 16 18 13 14 25 18 12 30 25 10 _ 6 0 75 10 6 1 16 10 1 5 25 16 2 5 32 35 4 45 32 6 _ 5 9 15 U 2 8 1 U 3 U 4 5 6 8 1 1 5 9 15 U...

Страница 17: ...6 4 R0 4 0 8 45 2 90 4 A 9 5 12 7 15 9 19 1 22 23 2 0 91 26 4 1 04 8 4 0 33 13 2 0 52 16 2 0 64 19 2 0 76 23 7 0 93 26 9 1 06 8 7 0 34 13 5 0 53 16 5 0 65 19 7 0 78 20 18 36 35 367 357 47 45 480 459 6...

Страница 18: ...90 1 7 1 10 17 16 3 7 3 9 3 2 0 5 0 4 0 2 1 6 7 1 2 7 1 2 26 3 9 0 03 4 5 65 6 2 5 0 4 1 6 2 7 1 9 5 S U 1 2 90 1 2...

Страница 19: ...404 900 1170 350 590 378 W H 3 5 5 5 5 6 M N P L H L 1 2H L A 1 2H L H L H L A H 9 8 25 11 8 30 L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or more 25 cm 9 8 or more 25 cm 9 8 or more 5 5 5...

Страница 20: ...1 5 2 5 13 12 2 4 6 3 1 2 3 4 57 4 67 67 4 5 8 4 9 4 1 5 2 5 3 5 1 2 3 60cm 23 6 M1 Fig 4 6...

Страница 21: ...10 11 Fig 4 4 Air inlet Grid 11 8 30 78 7 200 2 5 19 7 50 19 7 50 4 2 24 8 629 17 9 455 76 2 1935 18 0 456 4 3 1 2 3 4 5 6 4 4 1 2 1 2 1 M8 2 4 5 3 4 5 1...

Страница 22: ...9 8 L N 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 5 6 7 8 9 10 MC MC 10 14 17 18 21 23 25 4 1...

Страница 23: ...7 6 2 2 1 2 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 2 3 50 5 4 24 5 25 3 9 ST3 9 12 ST 2 9 10 AAA...

Страница 24: ...5 4 1 2 3 4 NEC 5 6 8 7 8 9 10 IEC 11 12 3 13 10 30 RCD 14 15 16 17 18 19 20 21 22 23 24 3 1 1 2...

Страница 25: ...3 2 04 09 10 07 13 13 14 15 16 09 08 1 2 5 3 4 6 17 17 19 20 20 21 7 8 L N 22 22 23 9 10 24 25 11 MC MC...

Отзывы: