6-35
ASDI Operations and Maintenance – TX Models – P/N: 52368
Full
Load
Voltage
Check
NOTE
Current flow depends on the applied voltage. Voltage lower than
the specified voltage causes low current and may negatively affect
operation. Make all measurements with the heater ON (Contactor
closed).
WARNING
These tests include high voltage. Exercise great caution in making
the following tests. Carelessness could result in severe injury or
death. See additional warnings located at the beginning of this
Chapter.
FULL
LOAD
VOLTAGE
CHECK
Check heater voltage by measuring voltage at the contactor terminals. See Data
sheet of your manual or rating plate on the vaporizer to determine the correct
voltage reading of your vaporizer. Measure voltage between all connected poles
of the contactor. The readings should be equal to +/- 3% of the value on the
rating plate.
Figure 12 – Full load voltage check
MEASURE VOLTAGE
CONTACTOR
CONTROL BOARD
POWER IN