ASDI
Installation, Operation and Maintenance Manual
– SECOND SUN – P/N 51856
17
Figure 9:
Heater and Pilot both turn off
NO
NO
HEATER AND PILOT BOTH TURN OFF
IS PRESSURE IN TANK ABOVE
160 PSI?
NO
ALLOW PRESSURE TO DROP BELOW
160 PSI BEFORE ATTEMPTING TO
RESTART HEATER.
REFILL TANK AND RESTART THE
HEATER USING STARTING
INSTRUCTIONS.
YES
OPEN VALVES AND FOLLOW STEPS 7
THROUGH 10 TO FINISH START UP
PROCEDURE.
ENSURE THERE ARE NO LEAKS IN HOSE
OR TUBING LEADING TO HEATER.
WIRING HARNESS IS DISCONNECTED OR
BROKEN. CHECK ALL WIRES AND
CONNECTIONS. SOLDER ALL WIRING REPAIRS
AND COVER REPAIR WITH HEAT SHRINK FOR
ADDITIONAL PROTECTION.
RESTART HEATER USING STARTING
INSTRUCTIONS GIVEN ON HEATER
COVER OR MANUAL.
IS PROPANE LEVEL IN
TANK BELOW PILOT
SECTION OF THE HEATER?
IS GAS TO HEATER TURNED OFF AT
ISOLATION VALVE TO VAPOR SPACE
OF TANK OR ON-OFF VALVE AT
CONTROLS SIDE OF TANK HEATER
COVER?
YES
YES
CAN A MV READING BE
OBTAINED ACROSS TERMINALS
2B, 3B AND 4B, 3B TO VERIFY
CONTINUITY?
YES
FOLLOW STARTING INSTRUCTIONS ON
BACK OF HEATER TO START THE UNIT.
NO
Содержание Second Sun
Страница 8: ...ASDI Installation Operation and Maintenance Manual SECOND SUN P N 51856...
Страница 12: ...4 ASDI Installation Operation and Maintenance Manual SECOND SUN P N 51856 This page is left intentionally blank...
Страница 26: ...18 ASDI Installation Operation and Maintenance Manual SECOND SUN P N 51856 Figure 10 Wiring Diagram...
Страница 29: ...ASDI Installation Operation and Maintenance Manual SECOND SUN P N 51856 21 APPENDIX A TECHNICAL INFORMATION...
Страница 32: ...24 ASDI Installation Operation and Maintenance Manual SECOND SUN P N 51856...
Страница 33: ...ASDI Installation Operation and Maintenance Manual SECOND SUN P N 51856 25...