background image

 

15

16. TROUBLESHOOTING 

 
Table 3 
 

 
No. 
 

Problem 

Possible cause 

Repair 

 

Water pressure in the 
system dropping slowly. 

Installation is not 
sealed. 

Check whether all welded connections, threaded 
connections, unions etc. are sealed. 

 

Radiators are cold at 
system’s maximum 
height and a low sound 
is heard. 

Air in the system and 
small pressure in the 
system. 

Increase system pressure and bleed the air from the 
system and radiators. 

 

 
Radiators are not heated 
along their entire length. 
 

Air in the radiators. 

Bleed the air from the radiators using release valve. 

Safety valve is not 
discharging water from 
the system and the 
pressure is below 3 
(2.5) bar. 

Faulty safety valve. 

Replace safety valve. 

Pressure in the system is 
over 3 (2.5) bar and 
safety valve is not 
discharging water from 
the system. 

Faulty safety valve. 

Replace safety valve. 

Sudden water 
temperature rise in the 
system. 

Air in the system. 

Bleed the air from the radiators. 

Valves toward radiators 
are shut. 

 
Open all valves in the heating system and enable 
normal water circulation in the system. 

Circulation pump 
failure. 

 
Repair or replace the circulation pump to enable 
heating system operation. 

Power outage. 

 
Open all valves that reduced the heating system and 
first of all, the by-pass valve. 
Stop making fire or make less fire and carefully 
monitor the system so that the water temperature does 
not exceed 90

°

C when the power is back on. 

 

Sudden water pressure 
rise in the system due to 
water temperature 
increase. 

 
Reduced expansion 
vessel pressure or 
vessel is completely 
empty. Remove the 
vessel’s lid or valve 
head and bleed some 
air through the valve. If 
the membrane is 
destroyed, water will 
leak from the valve and 
if only half-empty, only 
air will come out. 
 

If water is leaking from the valve, replace expansion 
vessel. 
Of only air is coming out from the valve, remove the 
vessel from the system and apply additional pumping. 
Vessel pressure should be equal to or higher than the 
height difference between the highest and lowest point 
of the system. Example: 
For a 5 m height difference, the pressure equals    
Pmin 

 0.5 bar. 

Air in the system. 

 
Release air from the system. 
 

Содержание ALFA TERM-27

Страница 1: ...STOVE USED FOR LOCAL HEATING ALFA TERM 27 INSTALLATION SETUP AND OPERATION INSTRUCTIONS...

Страница 2: ...IONS Width 315 mm Height min max 264 460 mm Depth 414 mm FIREBOX DOOR OPENING width height 175 200 mm FLOW AND RETURN PIPE CONNECTIONS R1 RS THERMO VALVE AND SAFETY VALVE CONNECTIONS R1 2 RU COOLING P...

Страница 3: ...pipe connection 21 Cleaning access plate 22 Handle 23 Grate support 24 Additional lid 25 Lever support 26 Tertiary air regulator knob 27 Tertiary air regulator cover 28 Cleaning access plate smaller...

Страница 4: ...4 Figure 1...

Страница 5: ...t and not on the side outlet The stove will reach its nominal heating capacity if the draft in the chimney is 20 Pa A chimney ensuring good draft is the basis of proper functioning of the stove The ch...

Страница 6: ...walls it must be well insulated If the chimney connection is tightly connected to the chimney if the connection is extended If it is properly cleaned and free of birds nests dirt and soot If the flue...

Страница 7: ...ation of the thermo valve safety pipe Item 6 is an R1 2 connection with an inner thread for safety valve installation 6 1 FLOW PIPE AND RETURN PIPE Fig 4 Items 1 and 2 and Fig 7 and 8 Items 3 and 10 T...

Страница 8: ...R1 2 connection Fig 4 Item 6 is welded at the back of the boiler under the cooktop frame on which a safety valve MUST be fitted The safety valve should be 2 5 to 3 bars You can fit it directly on the...

Страница 9: ...expansion vessel of 25 l and not more than 18 l which should be fitted on the return pipe as close to the boiler as possible and no block valves can be fitted between the boiler and expansion vessel...

Страница 10: ...pe connection 3 Distribution pipe 4 Open expansion vessel 5 Safety valve 6 Radiator valve 7 Radiator 8 Air release valve 09 Circulation pump 10 Return pipe 11 Spigot for filling and discharge 12 Safet...

Страница 11: ...em should be filled with water and well bled and the stove should be properly connected to the chimney as described in the foregoing items NOTE The stove may not be used without water It must be conne...

Страница 12: ...of the grate and pull it out of its holder Place the grate on the supports 4 pcs welded inside the boiler firebox at the front and in the back 2 2 pcs Fig 1 Item 23 Place the grate at an angle slante...

Страница 13: ...e damper used for starting the fire must be closed and power regulator must be open After you finish baking cooking or frying place the power regulator in desired position While baking increase the te...

Страница 14: ...cloth cleaning agents and mild detergent instead Clean the oven after each use while still hot After cleaning leave the oven door open for a few minutes to prevent bad odors the next time you heat the...

Страница 15: ...n all valves in the heating system and enable normal water circulation in the system Circulation pump failure Repair or replace the circulation pump to enable heating system operation Power outage Ope...

Страница 16: ...mp speed Replace pump nuts or the entire pump 10 Noise murmur coming from the heating system Pump speed is too high Lower the speed Air in the system Bleed the air from the heating system Loose knobs...

Страница 17: ...oor 17 Excessive heat for baking or cooking Thermostat set to a high temperature Reduce water temperature using the thermostat or burn a smaller fire 18 Boiler stove is smoking when used for the first...

Страница 18: ...ses if the damage has occurred during transportation after the device was sold if the defects occurred due to improper mounting improper maintenance or mechanical damaging by the buyer if the defect o...

Страница 19: ...19 Outline dimensions of ALFA TERM 27 stove Figure 16...

Отзывы: